Carrier ComfortVu TB-24-HM Installation And Operation Manual page 60

Bacnet thermostat standard (24 vac model)
Hide thumbs Also See for ComfortVu TB-24-HM:
Table of Contents

Advertisement

Technician Settings (cont.)
P122 – Cool Proportional output threshold time (seconds) (FC Only!)
Range:
0...100 seconds
Default:
60 seconds
P123 – Heat Proportional output threshold time (seconds) (FC Only!)
Range:
0...100 seconds
Default:
60 seconds
P160 – Minimum compressor ON time
Range:
0...20 minutes
Default:
2 minutes
P161 – Minimum compressor OFF time
Range:
0...20 minutes
Default:
13 minutes
P170 – Economizer low limit temperature
Range: 9...27ºC / 48...80ºF
Default: 17ºC / 63ºF
P187 – Display or hide humidity reading
"00" - Do not display humidity reading
"01" - Display humidity reading
P188 – Room temperature limit for disabling dehumidification in
unoccupied mode
Range:
10...30ºC / 50...85ºF
Default:
18ºC / 64ºF
- 60 -
Cool proportional
cooling threshold
Heat proportional
cooling threshold
Min. compressor
ON time
Min. Compressor
OFF time
Economizer low
limit temperature
(°C)
(°F)
Display or hide
humidity readings
Temp. for disabling
dehum. In unocc mode
(°C)
(°F)