DIP switch and jumper configurations
SW4.1 – Without valves control in FC config.
Enable = OFF (Open)
Disable = ON (Closed)
SW4.2 – Enable/Disable PIR detector
Enable = OFF (Open)
Disable = ON (Closed)
SW4.3 – Not used
Always OFF
SW4.4 - End of line resistor (120Ω)
OFF = Not end of line
ON = End of line
End of line
Communication line
SW1.1 through SW1.6, and SW3.1 through SW3.8
See Wiring and DIP switch/jumper settings (pages
25 through 39).
1
2
3
SW4
JP2JP3
1
2
3
4
5
6
SW1
End of line
- 21 -
4
1
2
3
4
5
6
7
8
SW3
JP2, JP3 – Outputs 15,16 – Analog or Digital
JP2 – Output 16
Position 1 -
Analog output
Position 3 -
Digital output
JP3 – Output 15
Position 1 -
Analog output
Position 3 -
Digital output