Switching on the Smart Line Module:
Fig. 1-5
Switching off the Smart Line Module:
To switch off the active line module, carry out the steps for switching it on in re-
verse order.
Switching off the controller with the OFF1 signal is delayed by the time entered in
p3490, thereby allowing the connected drives to be decelerated in a controlled
manner.
© Siemens AG, 2005. All rights reserved
SINAMICS S120 Function Manual, 06/05 Edition
POWER ON
S1: Power- -up inhibit
<2>
ZSWAE.0/1/2 = 0
"Commissioning complete"
(p10 = 0 and p9 = 0)
"0 = OFF1" (STWAE.0)
<2>
"0 = OFF2" (STWAE.1)
24 V at EP terminals
Power module
S2: Ready to start
<2>
ZSWAE.1/2/6 = 0
<3>
Line contactor is deenergized
Wait for power on
"0 = OFF1"
(STWAE.0)
<2>
p0862
ON
delay
S3a: Line contactor
line contactor
S3: Ready to run
ZSWAE.0/1 = 1
<2>
ZSWAE.2/6 = 0
Line contactor energized
Enable operation
(STWAE.3)
<2>
S4: Operation
ZSWAE.0/1/2 = 1
<2>
Pulses
Smart Infeed ramp-up
ZSWAE.6 = 1
3x
<3>
&
22
ZSWAE.0 = 1
<3>
&
T
21
<3>
Precharging
11
<3>
<1> POWER ON = 24 V electronics
&
<2> STWAE.xx = control word
00
<3>
ZSWAE.6 = 0
<3> r0002 = operating display
enabled
Supply
Smart infeed
supply OFF ----> ON
or RESET button
PROFIBUS supply bit xx,
ZSWAE.xx = status word
PROFIBUS supply bit xx
1-31