Configuration Tools; Class 2 Master; Local Operator Interface (Loi); Loi Button Operation/Loi Menu - Emerson Rosemount 3051 Series Quick Start Manual

Pressure transmitter/flow meter with profibus pa protocol
Hide thumbs Also See for Rosemount 3051 Series:
Table of Contents

Advertisement

February 2019
LOI – see
Class 2 master – see
5.4

Configuration tools

5.4.1 Local operator interface (LOI)

When ordered, the LOI can be used for commissioning the device. To activate
the LOI, push either configuration button located under the top tag of the
transmitter. See
information. The security jumper prevents changes made using the LOI.
Note
Buttons must be fully engaged ≈ 0.5 in. (10mm) of travel.
Table 5-1: LOI Button Operation
Button
(1)
Characters blink when they can be changed.
Figure 5-1: LOI Menu
5.5

Class 2 Master

The Rosemount 3051 Profibus DD and DTM files are available at
EmersonProcess.com/Rosemount
See
Table 5-2
Quick Start Guide
Table 5-1
and
Figure 5-1
Table 5-2
Table 5-1
and
Action
Navigation
Scroll
Moves down menu
categories
Enter
Selects menu
category
for steps to configure the transmitter for Pressure
for parameter configuration
Figure 5-1
for operation and menu
Character Entry
Changes character
(1)
value
Enters character
and advances
or by contacting your local salesperson.
Quick Start Guide
Save?
Changes between
Save and Cancel
Saves
19