Parameters

6 Parameters

6.1 Parameter Description

8-01 Control Site
Option:
[0] Digital and
ctrl.word
[1] Digital only
6
6
[2] Controlword
only
8-02 Control Word Source
Option:
[0]
None
[1]
FC RS485
[2]
FC USB
[3]
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
[30] External Can
28
®
VLT
Function:
The setting in this parameter overrides the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select.
Control by using both digital input and
control word.
Control by using digital inputs only.
Control by using control word only.
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the source of the control word: 1 of 2
serial interfaces or 4 installed options. During
initial power-up, the frequency converter
automatically sets this parameter to [3] Option
A, if it detects a valid fieldbus option installed
in slot A. When the option is removed, the
frequency converter detects a configuration
change, sets parameter 8-02 Control Word
Source to default setting [1] FC RS485, and
trips. If an option is installed after initial
power-up, the setting of
parameter 8-02 Control Word Source does not
change, but the frequency converter trips and
shows: Alarm 67, Option Changed.
When retrofitting a bus option into a
frequency converter that did not have a bus
option installed earlier, change the control to
bus-based. This change is required for safety
reasons to avoid an unintended change.
Danfoss A/S © 12/2015 All rights reserved.
DeviceNet MCA 104
8-03 Control Word Timeout Time
Range:
1 s
[ 0.1 -
*
18000 s]
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in parameter 8-03 Control Word Timeout Time.
Option:
[0]
Off
[1]
Freeze output Freezes output frequency until communi-
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1 Changes the set-up after a control word
[8]
Select setup 2 See [7] Select set-up 1.
[9]
Select setup 3 See [7] Select set-up 1.
[10] Select setup 4 See [7] Select set-up 1.
Function:
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it indicates
that the telegram communication has stopped.
The function selected in parameter 8-04 Control
Word Timeout Function is then carried out. A
valid control word triggers the timeout counter.
Function:
NOTICE
To change the set-up after a timeout,
configure as follows:
Set parameter 0-10 Active Set-up to [9]
Multi set-up and select the relevant
link in parameter 0-12 This Set-up
Linked to.
Resumes control via fieldbus (fieldbus or
standard), using the most recent control
word.
cation resumes.
Stops with auto restart when communi-
cation resumes.
Runs the motor at jog frequency until
communication resumes.
Runs the motor at maximum frequency until
communication resumes.
Stops the motor, then resets the frequency
converter to restart:
Via the fieldbus.
Via [Reset].
Via a digital input.
timeout. If communication resumes after a
timeout, parameter 8-05 End-of-Timeout
Function defines whether to resume the set-
up used before the timeout, or to retain the
set-up endorsed by the timeout function.
MG92F102