Parameter Access
5.3.4 Class ID 05h Connection Object
Class ID 05h connection object is a standard DeviceNet object for allocation and managing I/O and explicit messaging
connections. For this class, 3 instances are supported:
Explicit messages.
Polled I/O.
Change of state.
The attributes supported for the different instances are listed in Table 5.7, Table 5.8, and Table 5.9.
5
5
Attribute
1
2
3
4
5
6
7
8
9
12
13
14
15
16
17
Table 5.7 Instance 1 Attributes: Explicit Message Instance
20
VLT
Access
Name
Get
State
Get
Instance type
Get
Transport class
trigger
Get
Produced
connection ID
Get
Consumed
connection ID
Get
Initial
communication
characteristics
Get
Produced
connection size
Get
Consumed
connection size
Get/Set
Expected
package rate
Get
Watchdog
timeout action
Get
Produced
connection path
length
Get
Produced
connection path
Get
Consumed
connection path
length
Get
Consumed
connection path
Get
Production
inhibit time
Danfoss A/S © 12/2015 All rights reserved.
®
DeviceNet MCA 104
Data type
Description
USINT
State of the object.
USINT
Indicates either I/O or explicit message.
USINT
Defines behavior of the connection.
UINT
CAN identifier field when the connection transmits.
UINT
CAN identifier field value that denotes message to be received.
USINT
Defines the message group/groups across which productions and
consumptions associated with this connection occur.
UINT
Maximum number of bytes transmitted across this connection.
UINT
Maximum number of bytes received across this connection.
UINT
Defines value used in transmission trigger timer and inactivity/
watchdog timer.
USINT
Defines how to handle inactivity/watchdog timeout.
UINT
Number of bytes in the produced connection path attribute.
Array of USINT Specifies the application object/objects whose data is to be produced
by these connection objects.
UINT
Number of bytes in the consumed connection path attribute.
Array of USINT Specifies the application object/objects that are to receive the data
consumed by this connection object.
UINT
Defines minimum time between new data production. This attribute is
required for I/O client connection.