Control
4.5.2 Status Word under Instances 100/150,
101/151, and 102/152
Illustration 4.9 Status Words in Instances 150/151/152
Bit
Bit = 0
00
Control not ready
01
Drive not ready
02
Coasting
03
No error
04
No error
05
Reserved
06
No error
07
No warning
08
Speed reference
09
Local operation
10
Out of frequency limit
11
No operation
12
Drive ok
13
Voltage ok
14
Torque ok
15
Timer ok
Table 4.8 Status Bits
Explanation of the status bits:
Bit 00, Control not ready/ready
Bit 00 = 0: The frequency converter has tripped.
Bit 00 = 1: The frequency converter controls are ready, but
the power component is not necessarily receiving any
power supply (if there is 24 V external supply to controls).
Bit 01, Drive ready
Bit 01 = 1: The frequency converter is ready for operation.
Bit 02, Coasting stop
Bit 02 = 0: The frequency converter has released the motor.
Bit 02 = 1: The frequency converter can start the motor
when a start command is given.
Bit 03, No error/trip
Bit 03 = 0: The frequency converter is not in fault mode.
Bit 03 = 1: The frequency converter is tripped, and a reset
signal is required to re-establish operation.
Bit 04, No error/error (no trip)
Bit 04 = 0: The frequency converter is not in fault mode.
Bit 04 = 1: There is a frequency converter error but no trip.
Bit 05, Not used
Bit 05: Not used in the status word.
Bit 06, No error/trip lock
Bit 06 = 0: The frequency converter is not in fault mode.
Bit 06 = 1: The frequency converter is tripped and locked.
MG92F102
Programming Guide
Bit 07, No warning/warning
Bit 07 = 0: There are no warnings.
Bit 07 = 1: A warning has occurred.
Bit 08, Speed reference/speed = reference
Bit 08 = 0: The motor is running, but the present speed is
different from the preset speed reference. For example, it
could be the case while the speed is being ramped up/
down during start/stop.
Bit 08 = 1: The present motor speed matches the preset
speed reference.
Bit 09, Local operation/bus control
Bit = 1
Bit 09 = 0: [STOP/RESET] is activated on the control unit, or
Control ready
[2] Local in parameter 3-13 Reference Site is selected. It is
Drive ready
not possible to control the frequency converter via serial
Enable
communication.
Trip
Bit 09 = 1: It is possible to control the frequency converter
Error (no trip)
via the fieldbus/serial communication.
–
Bit 10, Out of frequency limit
Trip lock
Bit 10 = 0: The output frequency has reached the value in
Warning
parameter 4-52 Warning Speed Low or
Speed = reference
parameter 4-53 Warning Speed High.
Bus control
Bit 10 = 1: The output frequency is within the defined
Frequency limit ok
limits.
In operation
Bit 11, No operation/in operation
Stopped, auto start
Bit 11 = 0: The motor does not run.
Voltage exceeded
Bit 11 = 1: The frequency converter has a start signal, or
Torque exceeded
the output frequency is greater than 0 Hz.
Timer exceeded
Bit 12, Drive OK/stopped, auto start
Bit 12 = 0: There is no temporary overtemperature on the
inverter.
Bit 12 = 1: The inverter has stopped because of overtem-
perature, but the unit has not tripped and resumes
operation once the overtemperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13 = 0: There are no voltage warnings.
Bit 13 = 1: The DC voltage in the frequency converters DC
link is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14 = 0: The motor current is lower than the torque limit
selected in parameter 4-16 Torque Limit Motor Mode or
parameter 4-17 Torque Limit Generator Mode.
Bit 14 = 1: The torque limits in parameter 4-16 Torque Limit
Motor Mode and parameter 4-17 Torque Limit Generator
Mode are exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15 = 0: The timers for motor thermal protection and
frequency converter thermal protection, respectively, have
not exceeded 100%.
Bit 15 = 1: One of the timers has exceeded 100%.