Eaton W-VAC Series Instructions For Installation, Operation And Maintenance page 7

Vacuum circuit breaker
Table of Contents

Advertisement

 
  
SECTION 1: INTRODUCTION
The purpose of this book is to provide instructions for
unpacking, storage, installation, operation and mainte-
nance of Types W-VAC, W-VACR, and W-VACW
Vacuum Circuit Breakers. They are a horizontal drawout
type removable interrupting element design, unless
there is an "R" in the designation.The "R" as in W-VACR
indicates a fixed breaker configuration. They were
designed specifically to IEC 56 Standards for reliable
performance. All types can be applied in single tier or
double tier switchgear applications, with the basic
breaker element applicable to retrofitting. Reliable con-
trol and protection are achieved though the use of the
W-VAC family of breakers.
1-1 W-VAC, W-VACR AND W-VACW RATINGS
Table 1.1 Type W-VAC and W-VACW Vacuum Circuit Breaker Ratings
Circuit
Rated
Breaker
Voltage
Type
at
50-60HZ
 
kV
36W-VAC25
3.6
72W-VAC16
7.2
72W-VAC20
7.2
72W-VAC25
7.2
72W-VAC32
7.2
72W-VAC40
7.2
120W-VAC16
12
120W-VAC20
12
120W-VAC25
12
120W-VAC32
12
120W-VAC40
12
120W-VAC50
12
150W-VAC16
15
150W-VAC20
15
150W-VAC25
15
150W-VAC32
15
150W-VAC40
15
150W-VAC50
15
175W-VAC16
17.5
175W-VAC20
17.5
175W-VAC25
17.5
175W-VAC32
17.5
175W-VAC40
17.5
120W-VACW16
12
120W-VACW20
12
120W-VACW25
12
120W-VACW32
12
120W-VACW40
12
150W-VACW16
15
150W-VACW20
15
150W-VACW25
15
150W-VACW32
15
150W-VACW40
15
IB131009EN
 
Frequency
Rated Short Circuit
Breaking Current
& Short Circuit
Duration
Hz
kA
Sec
50/60
25
3
50/60
16
3
50/60
20
3
50/60
25
3
50/60
31.5
3
50/60
40
3
50/60
16
3
50/60
20
3
50/60
25
3
50/60
31.5
3
50/60
40
3
50/60
50
3
50/60
16
3
50/60
20
3
50/60
25
3
50/60
31.5
3
50/60
40
3
50/60
50
3
50/60
16
3
50/60
20
3
50/60
25
3
50/60
31.5
3
50/60
40
3
50/60
16
3
50/60
20
3
50/60
25
3
50/60
31.5
3
50/60
40
3
50/60
16
3
50/60
20
3
50/60
25
3
50/60
31.5
3
50/60
40
3
SATISFACTORY PERFORMANCE OF THESE
BREAKERS IS CONTINGENT UP-ON PROPER
APPLICATION, CORRECT INSTALLATION AND
ADEQUATE MAINTENANCE. THIS INSTRUCTION
BOOK MUST BE CAREFULLY READ AND FOL-
LOWED IN ORDER TO OBTAIN OPTIMUM PERFOR-
MANCE FOR LONG USEFUL LIFE OF THE CIRCUIT
BREAKERS.
TYPES W-VAC, W-VACR AND W-VACW BREAKERS
ARE PROTECTIVE DEVICES, AS SUCH, THEY ARE
MAXIMUM RATED DEVICES. THEREFORE, THEY
SHOULD NOT UNDER ANY CIRCUMSTANCES BE
APPLIED OUTSIDE THEIR NAMEPLATE RATINGS.
Rated Insulation Level
Lighting
Power
Pulse
Frequency
Withstand
Withstand
Voltage
Voltage
kV
kV
40
10
60
20
60
20
60
20
60
20
60
20
75
28
75
28
75
28
75
28
75
28
75
28
95
36
95
36
95
36
95
36
95
36
95
36
95
38
95
38
95
38
95
38
95
38
75
42
75
42
75
42
75
42
75
42
95
42
95
42
95
42
95
42
95
42
Instruction Book
WARNING
Rated Nominal Current
Short
Circuit
Making
Current
kA
(Peak) Amperes
63
630, 1250, 2000,3150
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000,3150
79
1250, 2000
100
3150
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000,3150
79
1250, 2000
100
1250, 2000,3150
125
3150
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000,3150
79
1250, 2000
100
3150
125
3150
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000,3150
79
630, 800, 1250, 1600
100
3150
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000
79
1250, 1600, 2000
100
1250, 2000
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000
79
1250, 2000
100
1250, 2000