Step 6: Withdraw Breaker from Test Position:
1. For the single tier configuration carriage assembly
version, lift the shoot bolt lever and pull the breaker
out. The breaker will close and trip as it comes out
from the Test position.
2. For the double tier configuration cradle assembly
version, retract the horizontal shoot bolts and pull
the breaker out. The breaker will close and trip as it
comes out from the Test position.