Applicable Standards; Error Messages And Troubleshooting Table - ABB SACE PR010/T Instructions Manual

Hide thumbs Also See for SACE PR010/T:
Table of Contents

Advertisement

6.6 Applicable standards

The SACE PR010/T test unit bears the CE quality mark and fully complies with all major
international standards on electromagnetic compatibility (EMC).
Emissions:
Electrostatic discharge:
Radiated immunity:
Conducted immunity:

6.7 Error messages and troubleshooting table

UPDATE ERROR
"SW updating failed"
"Press ESC to restart"
COMMUNICATION ERROR
"Communication error"
"Press ESC to return"
INVALID DIGITAL VOLTAGE
"DUT internal voltage not valid"
"Press ESC to return"
INVALID PROGRAM
"Program failed"
"Press ENTER for recovery"
ABB SACE
IEN55022 class B
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-6 (1kV)
This message indicates a software updating
error. To rectify, repeat the operation, after first
checking the PC-PR010/T connection and the
name of the loaded file.
This message indicates that the SACE PR010/
T's internal bus is unable to establish a
connection with the device under test.
This message indicates an internal DUT
voltage reading that is outside the accepted
range.
If this message is displayed when the SACE
PR010/T test unit is powered up, it means that
the program stored in the SACE PR010/T's
memory is incorrect due to the failure of a
previous software updating sequence.
In this situation, the SACE PR010/T test unit
cannot work and must therefore be reloaded
with the updated software.
SACE PR010/T
RH0025002
L2551
20
17/20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents