SACE PR010/T
test unit annex
ABB SACE
SACE PR010/T
RH0029002
L2551
EN

Advertisement

Table of Contents
loading

Summary of Contents for ABB SACE PR111

  • Page 1 SACE PR010/T test unit annex ABB SACE SACE PR010/T RH0029002 L2551...
  • Page 2: Table Of Contents

    6.1 Operation mode menu tree ..... . 19 Indications on operation ......20 ABB SACE SACE PR010/T...
  • Page 3 SACE PR111/P protection release ......21 7.1 Default setting for automatic PR111/P testing ..21 7.2 Operation mode menu tree .
  • Page 4 14.3.8 RC Test ........50 14.4 Measurements ....... . 50 ABB SACE SACE PR010/T...
  • Page 5 15.8 Status ........67 ABB SACE...
  • Page 6: Indications On The Functions Of The

    1. Indications on the functions of the unit SACE PR010/T (version SW 7.0) Electronic releases foreseen [also known as DUT (Device Under Test)]: SACE PR111 (in all IEC versions) SACE PR112 (in all IEC versions) SACE PR113 (in all IEC versions)
  • Page 7: Operation Mode Menu Tree

    SET with the dip switch provided. • The manual test may be performed either with electronic SET or with manual SET. In the case of manual test with manual SET, thresholds and curves must be selected with the dip-switches ABB SACE SACE PR010/T RH0029002...
  • Page 8 7. Select the type of setting used to test the protections with (User setting) 8. This appears: "Manual test with MAN parameters, press ENTER to proceed". 9. Select the protection function you want to test with 2. (S protection test) ABB SACE SACE PR010/T RH0029002 L2551 7/67...
  • Page 9: Sace Pr212/Mp Protection Release

    I-f: 2.00 => 800 A(*) sensor is 400A. 11. Select the phase (or phases) on which to simulate the (L1+L2+L3) fault current. 12. Press ENTER to activate fault simulation. 3. SACE PR212/MP protection release ABB SACE SACE PR010/T RH0029002 L2551 8/67...
  • Page 10: Operation Mode Menu Tree

    Change DUT protection parameters parameters (ELT) 2. Download Program DUT with default parameters for normal operation default parameters 3. Def. parameters 1. For test Define DUT protection parameters in PR010/T 2. Operative Define DUT protection parameters ABB SACE SACE PR010/T RH0029002 L2551 9/67...
  • Page 11: Indications On Operation

    Config. not valid To set the missing data, proceed as follows: 1. Press ENTER 2. Select the type of CB and the current rating of the CT 3. Store the settings by pressing ENTER ABB SACE SACE PR010/T RH0029002 L2551 10/67...
  • Page 12 4. Select the type of activity with 1 (Test) 5. Select the type of test with 1 (Protections) 6. Select the test mode with 1 (Automatic) 7. Pressing ENTER enables a simulation of the failure for each protection func- tion. ABB SACE SACE PR010/T RH0029002 L2551 11/67...
  • Page 13: Sace Pr222Ds Protection Release

    4. SACE PR222DS protection release ABB SACE SACE PR010/T RH0029002 L2551 12/67...
  • Page 14: Operation Mode Menu Tree

    Protections/Manual/Default set" parameters in the PR010/T 2. Operative Define default par. for: "Program/Default test unit download" 4.Communication Define communication par. for system bus Store par. parameters in the PR010/T test unit ABB SACE SACE PR010/T RH0029002 L2551 13/67...
  • Page 15: Indications On Operation

    Example of an automatic test application on the PR222DS release NOTE: the data indicating the type of CB and protection, the rated current of the CTs and the Neutral setting, are automatically identified by the PR010/T. ABB SACE SACE PR010/T RH0029002...
  • Page 16: Sace Pr222Mp Protection Release

    (Test) 4. Select the type of test (Protections) 5. Select the test mode with (Automatic) 6. Pressing ENTER enables a simulation of the failure for each protection function 5. SACE PR222MP protection release ABB SACE SACE PR010/T RH0029002 L2551 15/67...
  • Page 17: Operation Mode Menu Tree

    PR010/T 2. Operative Define DUT protection parameters 5.2 Indications on operation • The SACE PR010/T unit can be used only with SACE PR222MP protection releases with test connectors on the front. Test connector ABB SACE SACE PR010/T RH0029002 L2551 16/67...
  • Page 18 Example of an automatic test application on the PR222MP release NOTE: the data indicating the type of CB and protection and the current rating of the CTs are automatically identified by the PR010/T test unit. ABB SACE SACE PR010/T RH0029002...
  • Page 19: Sace Pr223Ef Protection Release

    5. Select the type of test with 1 (Protections) 6. Select the test mode with 1 (Automatic) 7. Pressing ENTER enables a simulation of the failure for each protection function 6. SACE PR223EF protection release ABB SACE SACE PR010/T RH0029002 L2551 18/67...
  • Page 20: Operation Mode Menu Tree

    Define default par. used for: "Test/ Store parameters test Protections/Manual/Default set" in the PR010/T test unit 2. Operative Define default par. for: "Program/Default download" 4. Communication Define communication par. for system bus Store protection par. unit parameters ABB SACE SACE PR010/T RH0029002 L2551 19/67...
  • Page 21: Indications On Operation

    3. Select the type of activity (Test) 4. Select the type of test (Protections) 5. Select the test mode (Automatic) 6. Pressing ENTER enables a simulation of the failure for each protection function. ABB SACE SACE PR010/T RH0029002 L2551 20/67...
  • Page 22: Sace Pr111/P Protection Release

    7. SACE PR111/P protection release TEST InN=In/2 7.1 Default setting for automatic PR111/P testing To test the protection functions in automatic mode, first set the PR111/P protection unit as follows: Protection Threshold Curve function 0.4 x In 3 x In C;...
  • Page 23: Indications On Operation

    (Protections) 8. Select the test mode with 1 (Automatic) [Make sure the default setting is programmed for automatic testing as shown under the heading "Default setting for automatic PR111/P testing"]. 8. SACE PR111/P-A protection release TEST LISTED InN=In/2 Low-Voltage AC...
  • Page 24: Default Setting For Automatic Pr111/P-A Testing

    7. Select the type of test with 1 (Protections) 8. Select the test mode with 1 (Automatic) [Make sure the default setting is programmed for automatic testing as shown under the heading "Default setting for automatic PR111/P-A testing"]. ABB SACE SACE PR010/T RH0029002 L2551 23/67...
  • Page 25: Pr112/P And Sace Pr112/Pd Protection Release

    SACE PR112/PD up Fault up Fault NETWORK Vaux WARNING EMERGENCY READ EDIT In = RESET TEST InN = In/2 Nr. = 9.2 Version without key (last letter in serial number M ÷ Z) ABB SACE SACE PR010/T RH0029002 L2551 24/67...
  • Page 26: Operation Mode Menu Tree

    3. Define default 1. Only for test 1. DUT config. Def. DUT configuration parameters 2. DUT Def. DUT parameters parameters 2. Operative 1. DUT config. Def. DUT configuration 2. DUT Def. DUT parameters parameters ABB SACE SACE PR010/T RH0029002 L2551 25/67...
  • Page 27: Indications On Operation

    • In this way the contact wear and number of operations indications will be reset to zero. WARNING Connect the test wire provided (between the SACE PR010/T and the SACE PR112) the right way round (see the adhesive labels on the connectors). ABB SACE SACE PR010/T RH0029002 L2551...
  • Page 28: Pr112/P-A And Sace Pr112/Pd-A Protection Release

    I-f: 2.00In => 4000 A(*) 10. Select the phase (or phases) on which to simulate the fault current (L1+L2+L3) 11. Press ENTER to activate fault simulation 10. PR112/P-A and SACE PR112/PD-A protection release ABB SACE SACE PR010/T RH0029002 L2551 27/67...
  • Page 29: Operation Mode Menu Tree

    1. Only for 1. DUT Define DUT configuration parameters test configur. parameters 2. DUT Define DUT protection parameters parameters 2. Operative 1. DUT Define DUT configuration configur. parameters 2. DUT Define DUT protection parameters parameters ABB SACE SACE PR010/T RH0029002 L2551 28/67...
  • Page 30: Indications On Operation

    T2: 0.4 s that I-F is lower than I3. I-f: 2.00 => 4000 A(*) 9. Select the phase (or phases) on which to simulate the fault current (L1+L2+L3) 10. Press ENTER to activate fault simulation. ABB SACE SACE PR010/T RH0029002 L2551 29/67...
  • Page 31: Sace Pr113/P And Pr113/Pd Protection Release

    1. DUT Read parameters configur. config. 2. DUT Read parameters param. 2 Operative 1. DUT Read configur. config. 2. DUT Read parameters param. 9. Information Read release identification, SW version and Serial Number ABB SACE SACE PR010/T RH0029002 L2551 30/67...
  • Page 32: Indications On Operation

    3. Select the type of activity with (Test) 4. Select the type of test with (Protections) 5. Select the test mode with (Automatic) 6. Pressing ENTER enables a simulation of the failure for each protection function. ABB SACE SACE PR010/T RH0029002 L2551 31/67...
  • Page 33: Sace Pr113/P-A And Pr113/Pd-A Protection Release

    3. Default parameters 1. For test 1. DUT config. Read config. 2. DUT param. Read param. 2 Operative 1. DUT config. Read config. 2. DUT param. Read param. 9. Information Read release identification, SW version and Serial Number ABB SACE SACE PR010/T RH0029002 L2551 32/67...
  • Page 34: Indications On Operation

    3. Select the type of activity with (Test) 4. Select the type of test with (Protections) 5. Select the test mode with (Automatic) 6. Pressing ENTER enables a simulation of the failure for each protection function ABB SACE SACE PR010/T RH0029002 L2551 33/67...
  • Page 35: Sace Pr121/P Protection Release

    2. Events display 3. Statistics 1. Display contact wear 2. Display total no. prot. trips 3. Display no. manual oper. 4. Display no. prot. oper. 5. Display no. trip failures 6. Display no. trip tests ABB SACE SACE PR010/T RH0029002 L2551 34/67...
  • Page 36: Indications On Operation

    • The automatic and manual tests must be performed with the circuit breaker off while the trip test may be performed only with the circuit breaker on; in either case the circulating currents must be null. ABB SACE SACE PR010/T RH0029002...
  • Page 37: Test

    For example, to perform the automatic test it is necessary to follow the procedure described in the following table: Key to be pressed Item selected Operation mode PR121/P Test Automatic test ENTER A brief description of the various tests will be given below. ABB SACE SACE PR010/T RH0029002 L2551 36/67...
  • Page 38: Automatic Test Of The Release Pr121/P

    With this test it is possible to send a command to turn off the circuit breaker, thus checking the functionality of the protection opening system. The trip test command is accepted by the protection unit only if the circuit breaker is on. ABB SACE SACE PR010/T RH0029002...
  • Page 39: Measurements

    For example to display the history of the openings (trip history), the following selections must be made: Key to be pressed Item selected Operation mode PR121/P History Trip history ENTER ABB SACE SACE PR010/T RH0029002 L2551 38/67...
  • Page 40: Configurations/Parameters

    Pressing the ENTER key launches editing mode (the cursor starts blinking); the buttons are used to position the cursor on the desired parameter and the buttons  and to change the value of the parameters in the allowed range. ABB SACE SACE PR010/T RH0029002 L2551...
  • Page 41 (the cursor starts blinking); the setting of the activation signal is changed using the keys  and If "Custom" is selected, when ENTER is pressed the current setting is displayed, for example: ALARM 1 4...6 → L Pre-alarm L Timing → S Timing ABB SACE SACE PR010/T RH0029002 L2551 40/67...
  • Page 42: Parameters

    Pressing the ENTER key launches editing mode (the cursor starts blinking); the buttons are used to position the cursor on the desired parameter and the buttons  and to change the value of the parameters in the allowed range. ABB SACE SACE PR010/T RH0029002 L2551...
  • Page 43: Information

    In particular, one or more of the following messages may be displayed: 1. No alarm 2. L Prealarm 3. T Prealarm 4. L1 Sensor error 5. L2 Sensor error 6. L3 Sensor error 7. Ne Sensor error ABB SACE SACE PR010/T RH0029002 L2551 42/67...
  • Page 44: Sace Pr122/P Protection Release

    11. Installation error 12. Device error 13. Invalid Date 14. Configuration error 15. CB status error Refer to the release user manual for the solution of the errors indicated. 14. SACE PR122/P protection release ABB SACE SACE PR010/T RH0029002 L2551 43/67...
  • Page 45: Operation Mode Menu Tree

    Display no. prot. operations Display no. trip failures Display no. trip tests 4. Config/Param 1. CONFIGURATIONS >> 2. PARAMETERS >> 5. Information 1. Protection unit information 2. Circuit breaker information 6. Status 1. Display configuration error ABB SACE SACE PR010/T RH0029002 L2551 44/67...
  • Page 46 8. Release 8 configuration 9. Data logger 1. Data logger configuration 2. Stop data logger event Display custom. type 3. Reset data logger 4. Stop data logger 10. System 1. Display clock 2. Set language ABB SACE SACE PR010/T RH0029002 L2551 45/67...
  • Page 47: Indications On Operation

    14.2 Indications on operation • The SACE PR010/T unit may be used with all SACE PR122/P releases connecting the test unit to the protection unit by means of a special cable to the functional test connector. ABB SACE SACE PR010/T RH0029002...
  • Page 48: Test

    8. Rc Test For example, to perform the automatic test it is necessary to follow the procedure described in the following table: Key to be pressed Item selected Operation mode PR122/P Test Automatic test ENTER ABB SACE SACE PR010/T RH0029002 L2551 47/67...
  • Page 49: Automatic Test Of The Release Pr122/P

    Phase Amplitude Phase shift Test Φ N° I [In] V[Un] 30° 0° 210° For example test n° 5 is performed with: IL = 0.3 In ABB SACE SACE PR010/T RH0029002 L2551 48/67...
  • Page 50: Manual Test

    14.3.7 Release output ZS Deactivates both the zone selectivity outputs of the protections S and G; this command allows checking of the zone selectivity function on the system. ABB SACE SACE PR010/T RH0029002 L2551...
  • Page 51: Rc Test

    For example to display the history of the openings (trip history), the following selections must be made: Key to be pressed Item selected Operation mode PR122/P History Trip history ENTER ABB SACE SACE PR010/T RH0029002 L2551 50/67...
  • Page 52: Configurations/Parameters

    Pressing the ENTER key launches editing mode (the cursor starts blinking); using the keys the cursor is positioned on the desired parameter and the keys  and are used to modify the value of the parameters in the allowed range. ABB SACE SACE PR010/T RH0029002 L2551...
  • Page 53: Local Bus Unit

    (the cursor starts blinking); the setting of the activation signal is changed using the keys  and If "Custom" is selected, when ENTER is pressed the current setting is displayed, for example: ALARM 1 4...6 → L Pre-alarm L Timing → S Timing ABB SACE SACE PR010/T RH0029002 L2551 52/67...
  • Page 54: Parameters

    13. UV prot. 14. OV prot. 15. RV prot. 16. RP prot. 17. UF prot. 18. OF prot. For example, selecting: Key to be Item selected pressed Operation mode PR122/P Config./Parameters Parameters Protection L ENTER ABB SACE SACE PR010/T RH0029002 L2551 53/67...
  • Page 55: Information

    ENTER enters the screen that displays information on the circuit breaker: Device: E1B800/4P Rated Current: xxxxA sn: xxxxxxxxxxxxxxxx Pressing the keys passes to the display of the next/previous screen: Install: xx/xx/xxxx Maint: xx/xx/xxxx ABB SACE SACE PR010/T RH0029002 L2551 54/67...
  • Page 56: Status

    11. Installation error 12. Device error 13. Invalid Date 14. Configuration error 15. CB status error Refer to the release user manual for the solution of the errors indicated. 15. SACE PR123/P protection release ABB SACE SACE PR010/T RH0029002 L2551 55/67...
  • Page 57: Operation Mode Menu Tree

    4. Config/Param 1. CONFIGURATIONS >> 2. Protection parameters 1. Set A PARAMETERS >> 2. Set B PARAMETERS >> 5. Information 1. Protection unit information 2. Circuit breaker information 6. Status 1. Display configuration error ABB SACE SACE PR010/T RH0029002 L2551 56/67...
  • Page 58 2. Release 1 configuration 1. Type of signal source Display custom. type 2. Display source configuration 3. Release 2 configuration 4. Release 3 configuration 5. Release 4 configuration 6. Release 6 configuration 7. Release 7 configuration ABB SACE SACE PR010/T RH0029002 L2551 57/67...
  • Page 59 13. Protection Rc parameters note 1 14. Protection MCR parameters 15. Protection UV parameters 16. Protection OV parameters 17. Protection RV parameters 18. Protection RP parameters 19. Protection UF parameters 20. Protection OF parameters ABB SACE SACE PR010/T RH0029002 L2551 58/67...
  • Page 60: Indications On Operation

    By means of the PR010/T unit it is possible to perform some tests on the protection unit, in particular: 1. Automatic test 2. Manual test 3. Trip test 4. Sign. mod. autotest 5. Force output S ZS 6. Force output G ZS ABB SACE SACE PR010/T RH0029002 L2551 59/67...
  • Page 61: Automatic Test Of The Release Pr123/P

    Phase Amplitude Phase shift Test Φ N° I [In] V[Un] 30° 0° 210° For example test n° 5 is performed with: IL1=0,3 In IL2=IL3= 0 In V12=V23=V31= 1 Un ABB SACE SACE PR010/T RH0029002 L2551 60/67...
  • Page 62: Manual Test

    15.3.7 Release output ZS Deactivates both the zone selectivity outputs of the protections S and G; this command allows checking of the zone selectivity function on the system. ABB SACE SACE PR010/T RH0029002 L2551 61/67...
  • Page 63: Rc Test

    For example to display the history of the openings (trip history), the following selections must be made: Key to be Item selected pressed Operation mode PR123/P History Trip history ENTER ABB SACE SACE PR010/T RH0029002 L2551 62/67...
  • Page 64: Configurations/Parameters

    Pressing the ENTER key launches editing mode (the cursor starts blinking); using the keys the cursor is positioned on the desired parameter and the keys  and are used to modify the value of the parameters in the allowed range. ABB SACE SACE PR010/T RH0029002 L2551...
  • Page 65 (the cursor starts blinking); the setting of the activation signal is changed using the keys  and If "Custom" is selected, when ENTER is pressed the current setting is displayed, for example: ALARM 1 4...6 → L Pre-alarm L Timing → S Timing ABB SACE SACE PR010/T RH0029002 L2551 64/67...
  • Page 66: Parameters

    10. LC1 prot. 11. LC2 prot. 12. Iw prot. 13. Rc prot. 14. MCR prot. 15. UV prot. 16. OV prot. 17. RV prot. 18. RP prot. 19. UF prot. 20. OF prot. ABB SACE SACE PR010/T RH0029002 L2551 65/67...
  • Page 67: Information

    The menu is divided into: 1. Protection unit 2. Circuit breaker For example, starting from the main menu, selecting: Key to be Item selected pressed Operation mode PR123/P Information Circuit breaker ENTER ABB SACE SACE PR010/T RH0029002 L2551 66/67...
  • Page 68: Status

    9. TC disconnected 10. Rating Plug error 11. Installation error 12. Device error 13. Invalid Date 14. Configuration error 15. CB status error Refer to the release manual for the solution of the errors signalled. ABB SACE SACE PR010/T RH0029002 L2551 67/67...