Scaling Of Preset References; Scaling Of Analog And Pulse References, And Feedback - Danfoss VLT 380-500 V Design Manual

Parallel drive modules
Table of Contents

Advertisement

Handling of References
P 3-00 Reference Range= [0] Min to Max
P 3-03
P 3-02
Illustration 15.4 Sum of All References

15.2 Scaling of Preset References

Preset references are indicated by units, which can be RPM,
m/s, bar, and so on. The preset references are scaled
according to the following rules:
When parameter 3-00 Reference Range= [0] Min to
Max , parameter 3-02 Minimum Reference is the
minimum reference (0%), and
parameter 3-03 Maximum Reference is the
maximum reference (100%). 50% reference is
found halfway between these 2 values.
When parameter 3-00 Reference Range=[1] -Max to
+Max , parameter 3-02 Minimum Reference is
ignored. Parameter 3-03 Maximum Reference is the
maximum reference (100%), which is used for the
+Max value (+100%) and the -Max value (-100%).
50% reference is found halfway between these 2
values.
15.3 Scaling of Analog and Pulse
References, and Feedback
References and feedback are scaled from analog and pulse
inputs in the same way. The only difference is that a
reference above or below the specified minimum and
maximum endpoints (P1 and P2 in Illustration 15.5) are
15
15
clamped, whereas feedback above or below is not.
138
Resulting reference
Danfoss A/S © 6/2016 All rights reserved.
®
VLT
Parallel Drive Modules
High reference/feedback
value
Terminal X low
-10
Sum of all
references
Illustration 15.5 Scaling of Analog and Pulse References
High reference/feedback
value
Terminal X low
-10
Illustration 15.6 Scaling of Analog and Pulse Feedback
The following parameters define the endpoints P1 and P2,
depending on which analog or pulse input is used.
Resource output
(RPM)
1500
0
-6
P1
Low reference/feedback value
-600
-1500
Resource output
(RPM)
1500
0
-6
P1
-600
Low reference/feedback value
-1500
P2
Resource
input
8
10
(V)
Terminal X
high
P2
Resource
input
8
10
(V)
Terminal X
high
MG37N102