Danfoss VLT 380-500 V Design Manual page 15

Parallel drive modules
Table of Contents

Advertisement

Product Overview
1
2
3
4
5
6
7
Area Title
Functions
1
Cabinet
Used to house the drive modules and other drive system components.
(installer-
provided)
2
DC busbars
Used to connect the DC terminals of the drive modules in parallel. The kit can be ordered from Danfoss or
(part of
fabricated by the panel builder.
busbar kit
option)
3
Wire harness
Used to link various components to the control shelf.
4
LCP
The local control module, shown mounted on the cabinet door. Allows the operator to monitor and control the
system and motor.
5
Control shelf
Consists of an MDCIC (multi-drive control interface card), a control card, an LCP, a safety relay, and an SMPS
(switched-mode power supply). The MDCIC interfaces the LCP and control card with the power card in each drive
module.
6
Drive modules 2 or 4 drive modules can be installed in parallel to create a drive system.
7
Busbar kit
Used to connect the motor, mains, and ground terminals of the drive modules in parallel. The kit can be either
(optional)
ordered from Danfoss as an optional kit or fabricated by the panel builder.
8
In-bottom/out-
Used to direct air in from the base of the enclosure, through the back channel of the drive module, and out
back cooling
through the top of the enclosure. Reduces heat inside the enclosure by 85%. The kit can be ordered from Danfoss
(optional)
as an optional kit. Refer to chapter 4.5.1 Back-channel Cooling Examples.
Illustration 4.4 Overview of 4-drive System without EMI/EMC Shields
MG37N102
Design Guide
Danfoss A/S © 6/2016 All rights reserved.
4
4
8
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt 525-690 v

Table of Contents