Danfoss VLT 380-500 V Design Manual page 75

Parallel drive modules
Table of Contents

Advertisement

Ordering Information
Illustration 7.10 Permanent Magnet (PM) Motor with Resolver
as Speed Feedback
Parameter 1-00 Configuration Mode
Parameter 1-01 Motor Control Principle
Parameter 1-10 Motor Construction
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 1-26 Motor Cont. Rated Torque
AMA is not possible on PM motors
Parameter 1-30 Stator Resistance (Rs)
Parameter 30-80 d-axis Inductance (Ld)
Parameter 1-39 Motor Poles
Parameter 1-40 Back EMF at 1000 RPM
Parameter 1-41 Motor Angle Offset
Parameter 17-50 Poles
Parameter 17-51 Input Voltage
Parameter 17-52 Input Frequency
Parameter 17-53 Transformation Ratio
Parameter 17-59 Resolver Interface
Table 7.12 Parameters to be Adjusted
MG37N102
Design Guide
Set-up example
In Illustration 7.9, a permanent magnet (PM) Motor is used
with resolver as speed feedback. A PM motor must usually
operate in flux mode.
Wiring
The maximum cable length is 150 m (492 ft) when a
twisted-pair type of cable is used.
NOTICE
Always use shielded motor cables and brake chopper
cables. Resolver cables must be shielded and separated
from the motor cables. The shield of the resolver cable
must be correctly connected to the decoupling plate and
connected to chassis (ground) on the motor side.
[1] Speed closed loop
[3] Flux with feedback
[1] PM, non-salient SPM
Nameplate
Nameplate
Nameplate
Motor datasheet
Motor datasheet (mH)
Motor datasheet
Motor datasheet
Motor datasheet (usually zero)
Resolver datasheet
Resolver datasheet
Resolver datasheet
Resolver datasheet
[1] Enabled