Danfoss VLT 380-500 V Design Manual page 142

Parallel drive modules
Table of Contents

Advertisement

Handling of References
Case 1. This case shows how reference input with limits inside minimum to maximum limits clamps.
Ext. Reference
Absolute
0 RPM 1 V
500 RPM 10 V
Digital input
Illustration 15.9 Positive Reference with Dead Band, Digital Input to Trigger Reverse
15
15
140
®
VLT
Parallel Drive Modules
General Reference
parameters:
Reference Range: Min - Max
Minimum Reference: 0 RPM (0,0%)
Maximum Reference: 500 RPM (100,0%)
Analog input 53
Low reference 0 RPM
+
High reference 500 RPM
Low voltage 1 V
High voltage 10 V
Ext. source 1
Range:
0,0% (0 RPM)
Reference is scaled
according to min max
100,0% (500 RPM)
RPM
500
V
10
1
Digital input 19
Low No reversing
High Reversing
Limits Speed Setpoint
according to min max speed
Danfoss A/S © 6/2016 All rights reserved.
General Motor
parameters:
Limited to: -200%- +200%
Motor speed direction: Both directions
(-1000 RPM- +1000 RPM)
Motor speed Low limit: 0 RPM
Motor speed high limit: 200 RPM
Ext. reference
Reference
Range:
algorithm
0,0% (0 RPM)
100,0% (500 RPM)
Reference
Range:
0,0% (0 RPM)
100,0% (500 RPM)
reference giving a speed
Scale to
speed
Speed
setpoint
Range:
-500 RPM
+500 RPM
Motor PID
Motor
control
Limited to:
0%- +100%
(0 RPM- +500 RPM)
Dead band
RPM
500
V
10
1
-500
Range:
Motor
-200 RPM
+200 RPM
MG37N102