Download Print this page

Select Application - Danfoss AK-LM 330 User Manual

Adap-kool refrigeration control systems
Hide thumbs Also See for AK-LM 330:

Advertisement

Select application

Measurements
AK error
Settings
Main switch
Configuration lock
Select quick setup
Thermostat 1 - 4
Measurements
AK error
No. of thermostats
Th1 temp.
Th 1 actual state
2, 3, 4
Settings
Main switch
Th1 Cut out temp
Th1 Cut in temp
Th1 High alarm limit
Th1 High alarm delay
Th1 High alarm del 2
Th1 Low alarm limit
Th1 Low alarm delay
Th1 DI def interlock
Th1 DI alarm disable
Th1 Sensor select
2, 3, 4
Thermostat 5 - 8
Measurements
AK error
5, 6, 7, 8
Settings
Main switch
5, 6, 7, 8
4
When "ON", the controller is in alarm condition.
Main switch:
Locking configuration
To implement changes of certain parameters, the configuration lock must be "open".
Note: "Main switch" must be turned" OFF" to open configuration
0: Open
1: Locked
Selection of predefined configurations.
When this is selected, all the controller settings and the definitions of input and out-
put will be adjusted to fit the selected application.
(see manual for more details on individual predefined settings).
When "ON", the controller is in alarm condition.
The number of thermostats that have been defined can be read here.
1 to 8 can be read and operated in the following menus.
9 or more can only be read and operated from the Service Tool AK-ST
Temperature Measurements on the sensor defined in "Thermostat 1"
The thermostat's actual value is shown here. ON or OFF.
There are similar settings for the other thermostats.
Main switch:
Cut out value for relay which is defined in "Thermostat 1"
Cut in value for relay which is defined in "Thermostat 1"
High alarm limit "Thermostat 1"
Delay time for high alarm "Thermostat 1" (normal regulation)
Delay time 2 for high alarm "Thermostat 1" (e.g. after a defrost / cooling down)
Low alarm limit "Thermostat 1"
Delay time for low alarm "Thermostat 1"
Definition of switch to "Delay time 2" with DI signal
0: not used
1-16: Here, it is defined which DI input is to activate the long delay time.
Definition of disarming alarm with DI signal
0: Not used
1-16: Here, the DI input that is to deactivate the alarm function is defined
Here, the sensor that is to be used for "Thermostat 1" is defined
There are similar settings for the other thermostats.
When "ON", the controller is in alarm condition.
Same function as for "Thermostat 1".
Main switch:
Same function as for "Thermostat 1".
Menu operation RC8CC202 © Danfoss 09/2012
ON:
Regulation
OFF: Controller stopped
ON:
Regulation
OFF: Controller stopped
ON:
Regulation
OFF: Controller stopped
AK-LM 330 Vers. 1.4x

Advertisement

loading