Control And Status Words - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
05.04
Fan on-time
counter
0...4294967295 d
05.11
Inverter
temperature %
-40.0 ... 160.0%
06
06 Control and status
words
06.01
Main control word
0000h...FFFFh
06.02
Application control
word
0000h...FFFFh
06.03
FBA A transparent
control word
00000000h ...
FFFFFFFFh
06.11
Main status word
0000h...FFFFh
Description
Running time of the drive cooling fan. Can be reset on the
control panel by keeping Reset depressed for over 3
seconds.
Cooling fan run-time counter.
Estimated drive temperature in percent of fault limit.
Drive temperature in percent.
Drive control and status words.
The main control word of the drive. This parameter shows the
control signals as received from the selected sources (such
as digital inputs, the fieldbus interface and the application
program).
The bit assignments of the word are as described on page
279. The related status word and state diagram are presented
on pages
280
and
281
respectively.
This parameter is read-only.
Main control word.
The drive control word received from the application program
(if any). The bit assignments are described on page 279.
This parameter is read-only.
Application program control word.
The unaltered control word received from the PLC through
fieldbus adapter A.
This parameter is read-only.
Control word received through fieldbus adapter A.
Main status word of the drive.
The bit assignments are described on page 280. The related
control word and state diagram are presented on pages
and
281
respectively.
This parameter is read-only.
Main status word.
Parameters 79
Def/FbEq16
-
1 = 1 d
-
1 = 1%
-
1 = 1
-
1 = 1
-
-
-
279
1 = 1