162 Parameters
No.
Name/Value
KTY84 StdIO /
Extension module
KTY84 module 1
KTY84 module 2
PT100 x1 StdIO
PT100 x2 StdIO
PT100 x3 StdIO
PTC DI6
PTC module 1
PTC module 2
Description
KTY84 sensor connected to the analog input selected by
parameter
35.24 Supervision 2 AI select
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation".
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
KTY84 sensor connected to encoder interface 1.
See also parameters
91.21 Temperature meas sel1
91.22 Temperature filtering time
KTY84 sensor connected to encoder interface 2.
See also parameters
91.24 Temperature meas sel2
91.25 Temperature filtering time
Pt100 sensor connected to the analog input selected by
parameter
35.24 Supervision 2 AI select
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to U (voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
12 Standard AI
• In parameter group
13 Standard
selection parameter of the analog output to
excitation".
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
As selection
PT100 x1
StdIO, but with two sensors connected
in series. Using multiple sensors improves measurement
accuracy significantly.
As selection
PT100 x1
StdIO, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
PTC sensor connected to digital input DI6.
PTC sensor connected to encoder interface 1.
See also parameters
91.21 Temperature meas
Temperature filtering time 1
PTC sensor connected to encoder interface 2.
See also parameters
91.24 Temperature meas
Temperature filtering time 2
and an analog
to
V
(volt).
AO, set the source
"Force KTY84
1.
2.
and an analog
to
V
(volt).
AO, set the source
"Force PT100
sel1,
and
91.23 PTC filtering
sel2,
and
91.26 PTC filtering
Def/FbEq16
2
3
and
4
and
5
6
7
8
9
91.22
1.
10
91.25
2.

Hide quick links: