66 Application macros

Torque control macro

This macro is used in applications in which torque control of the motor is required.
Torque reference is given through analog input AI2, typically as a current signal in the
range of 0...20 mA (corresponding to 0...100% of rated motor torque).
The start/stop signal is connected to digital input DI1. The direction is determined by
DI2.
Through digital input DI3, it is possible to select speed control instead of torque
control. It is also possible to change the control to local (control panel or PC tool) by
pressing the Loc/Rem key. By default, the local reference is speed; if a torque
reference is required, the value of parameter
changed to Torque.
A constant speed (by default, 300 rpm) can be activated through DI4. DI5 switches
between acceleration/deceleration time sets 1 and 2. The acceleration and
deceleration times, as well as ramp shapes, are defined by parameters
23.12...23.19.

Default parameter settings for the Torque control macro

Below is a listing of default parameter values that differ from those listed for the
Factory macro in
Additional parameter data
Parameter
No.
Name
19.11
Ext1/Ext2 selection
19.14
Ext2 control mode 1
20.06
Ext2 commands
20.08
Ext2 in1
20.09
Ext2 in2
22.12
Speed ref2 selection
22.14
Speed ref1/2 selection
22.22
Constant speed sel1
23.11
Ramp set selection
26.11
Torque ref1 selection
31.11
Fault reset selection
19.16 Local control mode
(page 225).
Torque control macro
default
DI3
Torque
In1 Start; In2 Dir
DI1
DI2
AI2 scaled
DI3
DI4
DI5
AI2 scaled
Off
should be