152 Parameters
No.
Name/Value
32.17
Superv2 signal
32.18
Superv2 filter time
0.000 ... 30.000 s
32.19
Superv2 lo
-21474836.48 ...
21474836.47
32.20
Superv2 hi
-21474836.48 ...
21474836.47
32.25
Superv3 function
Disabled
Low
High
Abs Low
Abs High
Both
Abs Both
32.26
Superv3 action
No
Warning
Fault
32.27
Superv3 signal
32.28
Superv3 filter time
0.000 ... 30.000 s
32.29
Superv3 lo
-21474836.48 ...
21474836.47
Description
Selects the signal to be monitored by signal supervision
function 2.
For the available selections, see parameter
signal.
Defines the filter time constant for signal supervision 2.
Signal filter time.
Defines the lower limit for signal supervision 2.
Low limit.
Defines the upper limit for signal supervision 2.
Upper limit.
Selects the mode of signal supervision function 3. Determines
how the monitored signal (see parameter 32.27) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.26.
Signal supervision 3 not in use.
Action is taken whenever the signal falls below its lower limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Selects the action the drive takes when the value monitored
by signal supervision 3 exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No action taken.
A warning
(A8B0 Signal
The drive trips on
80B0 Signal
Selects the signal to be monitored by signal supervision
function 3.
For the available selections, see parameter
signal.
Defines the filter time constant for signal supervision 3.
Signal filter time.
Defines the lower limit for signal supervision 3.
Low limit.
32.07 Superv1
(32.29
and
32.30
respectively).
supervision) is generated.
supervision.
32.07 Superv1
Def/FbEq16
Zero
0.000 s
1000 = 1 s
0.00
-
0.00
-
Disabled
0
1
2
3
4
5
6
No
0
1
2
Zero
0.000 s
1000 = 1 s
0.00
-