Parameter assignment/Addressing
5.1 MODBUS RTU
Table 5-26
Parameters supported by the broadcast commands
Offset
Number of
registers
50023
2
63021
2
63023
2
63025
2
60005
1
60006
1
60009
1
1) Only for the PAC RS485 expansion module
56
Name
Format
Synchronization
Unsigned long
Baud rate
Unsigned long
1)
Data bits / Parity
Unsigned long
bits / Stop bits
1)
Response time
Unsigned long
1)
Synchronization of
Unsigned short •
the demand period
in minutes
Switching tariff
Unsigned short •
Switching
Unsigned short •
command for
vector group
Applicable
Value range
MODBUS
function codes
0x03
0 =
No synchronization
0x04
1 =
Synchronization
0x10
2 =
0x03
0 = 4,800 bit/s
1 = 9,600 bit/s
0x04
2 = 19,200 bit/s
0x10
3 = 38,400 bit/s
Standard value = 2
0x03
0 =
0x04
1 =
0x10
2 =
3 =
0x03
0 ... 255
0 = Auto
0x04
0x10
0x06
1 ... 60
0x06
0 =
1 =
0x06
High 0 ... 99, Low 0 ... 1
High Byte
Group assignment
Low Byte 1 = ON, 0 = OFF
Manual, 02/2008, A5E02091800B-01
Access
RW
via bus
Synchronization
via the digital input
RW
8N2
RW
8E1
8O1
8N1
RW
W
High tariff
W
Low tariff
W
PAC RS485