Modbus register map
6.6.3 Register addresses 40201 to 40215: Metered measurands
•
Data type definition ref. to chap. 5.4,
•
Registers are write-protected
Scaling
Example
Register
Designation of the
address
SIPROTEC objects
40201
Wp(puls) =
–
40202
40203
Wq(puls) =
–
40204
40205
WpForward=
–
40206
40207
WqForward=
–
40208
40209
WpReverse =
–
40210
40211
WqReverse =
–
40212
40213
Op.Hours=
–
40214
6-28
7
.
The scaling of the metered measurands, which are derived from
measured values, refers to:
60000 impulses per hour for V = V
V
= P
O
RIMARY
PERATING
prim
(parameter address = 1101)
I
=
P
O
RIMARY
PERATING
prim
(parameter address = 1102)
In the parameter set is configured:
I
= 100 A und V
prim
60000 impulses correspond so that:
1 h * 100 A * 12 kV *
Note
The type of the update (cyclic, with or without deletion) and the update
interval must be programmed for the metered measurands (except for
the operating hours meter) with the parameterization software DIGSI.
Comments
Pulsed Energy Wp (active)
(metering impulses at binary input)
Pulsed Energy Wq (reactive)
(metering impulses at binary input)
Wp Forward
(metered measurand derived from
measured value)
Wq Forward
(metered measurand derived from
measured value )
Wp Reverse
(metered measurand derived from
measured value)
Wq Reverse
(metered measurand derived fom
measured value)
Counter of operating hours of the
primary equipment
and I = I
prim
V
OLTAGE
C
URRENT
= 12 kV,
prim
3
= 2078.46 kWh
Scaling
31
(2
-1 of the unsigned long
value corresponds to...)
31
2
-1 impulses
31
2
-1 impulses
31
2
-1 impulses
31
2
-1 impulses
31
2
-1 impulses
31
2
-1 impulses
31
2
-1 hours
7SJ61/62/63 6MD63 – Modbus
prim
Internal
object
no.
888
889
924
925
928
929
1020
C53000-L1840-C001-01