Register
Designation of the
address
SIPROTEC objects
10057
CFC-Output indication 9
(UsCfcSpO9)
10058
CFC-Output indication 10
(UsCfcSpO10)
10059
CFC-Output indication 11
(UsCfcSpO11)
10060
CFC-Output indication 12
(UsCfcSpO12)
10061
CFC-Output indication 13
(UsCfcSpO13)
10062
CFC-Output indication 14
(UsCfcSpO14)
10063
CFC-Output indication 15
(UsCfcSpO15)
10064
CFC-Output indication 16
(UsCfcSpO16)

6.4.3 Register addresses 10065 to 10089: Automatic recloser status

Register
Designation of the
address
SIPROTEC objects
10065
>79 ON
10066
>79 OFF
10067
>BLOCK 79
10068
>79 T WAIT
10069
> 79 TRIP 1p
10070
> 79 TRIP 3p
10071
>Enable ANSI#-2
10072
>CB Ready
10073
79AR OFF
4
10074
reserved
10075
CB is NOT ready
10076
79 DynBlock
10077
79 in progress
10078
79 Close
10079
79 Successful
10080
79 Lockout
10081
79 L-N Sequence
7SJ61/62/63 6MD63 - Modbus
C53000-L1840-C001-01
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Single-point indication ON/OFF,
released as CFC output
Note
The CFC-Output indications allow configuration of further protection
annunciations on Modbus registers, which are not contained in the
standard mapping.
1 = >79 ON
1 = >79 OFF
1 = >BLOCK 79
1 = >79 T Wait (coordination control)
1 = >79 Ext. 1pole TRIP for internal A/R
1 = >79 Ext. 3pole TRIP for internal A/R
1 = >Enable 50/67-(N)-2 (override 79 blk)
1 = >Circuit breaker READY for reclosing
1 = 79 Auto recloser is switched OFF
1 = Circuit breaker is NOT ready
1 = 79 - Auto-reclose is dynamically BLOCKED
1 = 79 - in progress
1 = 79 - Close command
1 = 79 - cycle successful
1 = 79 - Lockout
1 = 79-A/R single phase reclosing sequence
Modbus register map
Comments
Comments
Internal
object no.
Internal
object no.
2701
2702
2703
2705
2715
2716
2720
2730
2781
2784
2785
2801
2851
2862
2863
2878