Holding Registers (4X References); Register Addresses 40001 To 40048: System Information; Register Address 40129: Diagnosis - Siemens SIPROTEC 7SJ61 Technical Data Manual

Multifunction protection with control
Hide thumbs Also See for SIPROTEC 7SJ61:
Table of Contents

Advertisement

Modbus register map
6.6

Holding registers (4X references)

6.6.1 Register addresses 40001 to 40048: System information

Registers are write-protected
Register
Designation
address
40001
Hardware designation of the
communication module
40008
(string, max. 16 characters)
40009
Communication module software
revision
40010
40011
MLFB (order number) of the
SIPROTEC device
40026
(string, max. 32 characters)
40027
Date and time of mapping data
generation
40034
(string, max. 16 characters)
40035
Number of selected standard
mapping ,
40036
Revision of mapping data

6.6.2 Register address 40129: Diagnosis

Registers are write-protected
The contents of these registers are also readable using function "Diagnostics" (function code 7), subfunction
"Return Diagnostic Register" (subfunction code 2).
Register
Designation of the
address
SIPROTEC objects
0
40129 / 2
Device OK
1
40129 / 2
reserved
2
40129 / 2
Settings Calc.
3
40129 / 2
Chatter ON
4
40129 / 2
Error Sum Alarm
7
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
6-26
The holding register block allows the Modbus master to read system
information, measured values – mean values, metered measurands as
well as fault locations.
Note
Depending on the device composition not all of the indicated measured
values/metered measurands (and corresponding Modbus registers) may
be available in the SIPROTEC device.
7
.
"AME-GEN" for AME module,
"AMO-GEN" for AMO module
Example:
Register 40009 = 0001H, Register 40010 = 0205H
-> Revision 1.2.5
Example:
"7SJ63254EA903HG3----0D----------"
Example:
"140100095747330" corresponds to
Date: 14
Time: 09 hours 57 min. 47 seconds and 330 milliseconds
MSB of register 40035:
Number of selected standard mapping,
LSB of register 40035 and value of register 40036:
Revision of mapping data.
Example:
Register 40035 = 0102H, Register 40036 = 0304H
-> Standard mapping 1, Revision 2.3.4
7
,
1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart
= 0
1 = Setting calculation is running
1 = Chatter ON
1 = Error with a summary alarm ON
Comments
th
Jan 2000,
Comments
7SJ61/62/63 6MD63 – Modbus
C53000-L1840-C001-01
Internal
object no.
51
70
125
140