Register Addresses 40251 To 40257: Measured Values - Mean Values - Siemens SIPROTEC 7SJ61 Technical Data Manual

Multifunction protection with control
Hide thumbs Also See for SIPROTEC 7SJ61:
Table of Contents

Advertisement

6.6.4 Register addresses 40251 to 40257: Measured values – mean values
Data type definition ref. to chap. 5.3,
Registers are write-protected
Explanations for selecting a standard mapping ref. to chap. Kap. 6.5.1.
Register
Designation of the
address
SIPROTEC objects
40251
Ia dmd=
40252
Ib dmd=
40253
Ic dmd=
40254
I1dmd =
40255
Pdmd =
40256
Qdmd =
40257
Sdmd =
7SJ61/62/63 6MD63 - Modbus
C53000-L1840-C001-01
Note
The scaling of the metered measurands at binary inputs ("Wp(puls)"
and "Wq(puls)") depends on the externally connected pulse
generator.
The error status bit of the metered measurands (except of the
operating hours meter) is set after a initial start or restart of the
SIPROTEC device until the second update cycle of the metered
measurands after the reset. This indicates the metered measurands
as "invalid by reset".
The error status bit of the metered measurand also signals the
condition of the external fault input of the metered measurands at
binary input (as far as this is parameterized).
7
,
Comments
I A demand
I B demand
I C demand
I1 (positive sequence)
Demand
Active Power Demand
Reactive Power Demand
Apparent Power Demand
Modbus register map
Scaling
(32767 corresponds to ...)
1: 3276.7 A
2: 32.767 kA
3: 3276.7 A
1: 3276.7 A
2: 32.767 kA
3: 3276.7 A
1: 3276.7 A
2: 32.767 kA
3: 3276.7 A
1: 3276.7 A
2: 32.767 kA
3: 3276.7 A
1: 327.67 MW
2: 327.67 MW
3: 3276.7 kW
1: 327.67 MVAR
2: 327.67 MVAR
3: 3276.7 kVAR
1: 327.67 MVAR
2: 327.67 MVAR
3: 3276.7 kVAR
Internal
object no.
963
964
965
833
834
835
836