Register
Designation of the
address
SIPROTEC objects
00092
CFC-Incoming annunciation 12
(UsCfcSpI12)
00093
CFC-Incoming annunciation 13
(UsCfcSpI13)
00094
CFC-Incoming annunciation 14
(UsCfcSpI14)
00095
CFC-Incoming annunciation 15
(UsCfcSpI15)
00096
CFC-Incoming annunciation 16
(UsCfcSpI16)
Example
7SJ61/62/63 6MD63 - Modbus
C53000-L1840-C001-01
Tagging ON/OFF,
released as CFC input
Tagging ON/OFF,
released as CFC input
Tagging ON/OFF,
released as CFC input
Tagging ON/OFF,
released as CFC input
Tagging ON/OFF,
released as CFC input
Note
The CFC-Incoming annunciations allow routing of further protection
annunciations on Modbus registers, which are not contained in the
standard mapping (e.g. ">BLK 50/51", internal object number = 1704 or
">BLK 50N/51N", internal object number = 1714).
Control of object ">BLK 50/51" using "CFC-Incoming annunciation 1
(UsCfcSpI1)" via Modbus:
•
In the DIGSI configuration matrix set the source for ">BLK 50/51" to
CFC output.
•
All CFC-Incoming annunciations are released as CFC input by
default, therefore no further actions in the DIGSI configuration matrix
are nessesary.
•
Open a CFC working page and insert a CONNECT module.
•
Connect the input („BO X") of the CONNECT module with the
operand "UsCfcSpI1" (group „Protocol").
•
Connect the output („Y BO") of the CONNECT module with the
operand ">BLK 50/51" (Gruppe: "50/51 Overcur.").
•
Save and translate the CFC working page.
The object ">BLK 50/51" (and with that the associated protective
function) can be influenced by changing the value of the "CFC-Incoming
annunciation 1" via Modbus now.
Modbus register map
Comments
Internal
object no.
–
–
–
–
–
6-7