Parameter Settings Table - Rinnai I Series Installation And Operation Manual

Wall-mounted, gas-fired combi boiler, central heating and domestic hot water
Hide thumbs Also See for I Series:
Table of Contents

Advertisement

Parameter
Number
Pressure Indication on the Control Panel
The current pressure will cycle on the controller
00
display. If an external pressure gauge is present,
it is permissible to change the setting to "No."
Outdoor Reset Curve
This parameter is available when Dip Switch 1 is
in the OFF (default) position. Select the proper
curve from below. See section "12.5 Outdoor
Reset Control" for more information.
Curve 1: Standard baseboard, high efficiency air
01
handler, cast iron or panel radiators.
Curve 2: Staple up radiant.
Curve 3: High temperature air handler or
undersized baseboard.
Curve 4: Custom curve based on customer
input.
Boost
This parameter is available when Dip Switch 1 is
in the OFF (default) position.
02
Boost mode works when the outdoor sensor
detects higher outdoor temperatures than
expected.
Maximum Outdoor Temperature the Boiler will
Fire in CH Mode
This parameter is available when DIP switch 1 is
in the OFF (default) position.
03
This sets the maximum outdoor temperature
the boiler will fire in CH mode. This can prevent
the boiler from firing in warm outdoor
temperatures.
Maximum DHW Set Point Temperature
This selects the maximum DHW set point
10
temperature. When 140°F, it is recommended
to have a mixing valve to prevent scalding.
How Long Diverter Valve in DHW Position
This selects the length of time the 3 Way Valve
will stay in the DHW position after using DHW
11
even if a CH demand is present.
While the 3 Way Valve is in the DHW position,
this enables quicker delivery of hot water.
DHW Recirculation Piping Setup
This parameter is available when DIP switch 3 is
in the ON position. This sets the DHW
12
recirculation piping mode, which controls the
circulation logic. Ensure this corresponds to the
DHW recirculation piping.
Rinnai I-Series Condensing Boiler Combi Manual
Setting Description
Selection
A
b
Yes
No
Curve
Curve
1
2
30
No
Minutes
No
77°F
Maximum
(25°C)
120°F
140°F
(49°C)
(60°C)
3
10
Minutes
Seconds
Crossover
Dedicated
Valve
Return
C
d
Curve
Curve
3
4
60
Minutes
85