Rinnai I Series Technical Bulletin

Rinnai I Series Technical Bulletin

Boiler with dhw recirculation
Hide thumbs Also See for I Series:

Advertisement

Technical Bulletin 158 - I-Series Boiler with DHW Recirculation
PURPOSE: To announce the I-Series Condensing Combi Boiler offers DHW recirculation and to explain
how DHW recirculation works, the different recirculation modes, and how to configure the boiler for
DHW recirculation.
I-Series Condensing Combi Boiler Models: i060C, i090C, and i120C

DHW Recirculation Facts:

Recirculation circulates hot water through the plumbing system, so hot water is always available in
whatever part of the house that the consumer may need it.
Recirculation requires an external recirculation pump. For pump sizing, reference the "DHW
Pressure Drop and Flow Curve" in the Boiler Installation and Operation Manual.
An optional 24V timer can be used to set the time intervals and duration of recirculation (an
example timer is the Intermatic® MIL72ASTUZ-24).
Two recirculation modes are available: Dedicated and Crossover:

Dedicated Mode:

The plumbing system includes a dedicated hot water
return line.
Recirculation technology in the boiler decides if the
pump will turn on based on time intervals and DHW
setpoint temperature.
How the recirculation pump works:
The pump turns ON and runs until the DHW
return water temperature is within 6°F of the
setpoint temperature, or for 20 minutes,
whichever occurs first.
The pump stays OFF based on the DHW setpoint
temperature (as outlined in the table below).
DHW Setpoint
140° 135° 130° 125° 120° 115° 110° 108° 106° 104° 102° 100° 98°
Temperature (°F)
Typical Pump OFF
Intervals (Minutes)
Note: Rinnai strongly recommends installing insulation to the hot water and dedicated return lines
to decrease the amount of heat loss.
9
10
11
12
Cold water
Home includes dedicated hot water
and cold water lines.
14
16
19
20
Hot water
22
24
26
28
TB-158
7/2019
31

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the I Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rinnai I Series

  • Page 1 140° 135° 130° 125° 120° 115° 110° 108° 106° 104° 102° 100° 98° Temperature (°F) Typical Pump OFF Intervals (Minutes) Note: Rinnai strongly recommends installing insulation to the hot water and dedicated return lines to decrease the amount of heat loss. TB-158 7/2019...
  • Page 2 Dedicated Mode Plumbing Diagram IMPORTANT This diagram is not a complete piping diagram; it shows DHW piping only (Central Heating piping is not displayed). Refer to the Boiler Installation and Operation Manual for a complete piping diagram. Recirculation Pump Wiring Timer (Optional) Gas Supply Line...
  • Page 3 When installed, the boiler uses the cold water line for hot water recirculation. A thermal bypass valve can be purchased through Rinnai (PN: 107000143) or plumbing supply stores. • How the recirculation pump works: −...
  • Page 4 Configure the Boiler for DHW Recirculation: Step 1: Set DIP Switches and Parameter Settings Note: Refer to the Boiler Installation and Operation Manual for complete DIP Switch and Parameter Setting instructions. 1. Remove the boiler’s front panel. 2. Locate the PC Board (lower left side of unit). 3.
  • Page 5 Step 2: Connect Wiring to PC Board 6. Wire the external DHW recirculation pump to the DHW_Pump Terminal connection on the PC Board (see A below). 7. If using a timer: • Wire the 24V AC timer circuit to the 24V AC for External Output connection (see B). •...

This manual is also suitable for:

I060c, i090cI120cI120cn

Table of Contents