Common Ch Components - Rinnai I Series Installation And Operation Manual

Wall-mounted, gas-fired combi boiler, central heating and domestic hot water
Hide thumbs Also See for I Series:
Table of Contents

Advertisement

Plumb the heating supply line to the
heating supply connection on the
bottom of the boiler.
Heating Supply Connection
Listed below are common components in a
Central Heating system. Refer to the diagram
on the next page.
Expansion Tank — A properly sized
expansion tank charged to 2 PSI (14 kPa)
below the cold system pressure is required
to limit pressure changes in the heating
system. When replacing an expansion tank,
consult the expansion tank manufacturer
for sizing.
Air Separator — An air separator is needed
on the central heating supply side of the
system to remove any air that may be
present in the piping.
Pressure/Temperature Gauge — The
current pressure and temperature will
alternately be displayed on the boiler
control panel. A port for an external gauge
is present in the Primary-Secondary
Heating Kit accessory offered by Rinnai.
Rinnai I-Series Condensing Boiler Combi Manual
Pressure Relief Valve (PRV) — A PRV
located directly on the supply side of
the boiler is required. The PRV must be
3/4 in. with at least 30 PSI (207 kPa)
and a maximum of 45 PSI (310 kPa). A
30 PSI (207 kPa) PRV is supplied with
the boiler. A port for the central
heating PRV is present in the Primary-
Secondary Heating Kit accessory
offered by Rinnai.
Oxygen Elimination — The boiler may
only be installed in a pressurized closed
-loop heating system, free of air and
other impurities. If using oxygen
permeable tubing in the central heating
system, a plate heat exchanger is
necessary to isolate the tubing and
boiler.
Low Water Cut Off (LWCO) — This
boiler has a factory-installed pressure
sensor type LWCO. The boiler's internal
LWCO is not serviceable or adjustable.
Check your local codes to determine if
a LWCO is required and if this device
conforms to the local code. If a LWCO is
required to be installed, the probe
must be located higher than the
minimum safe water level. When a
LWCO is installed, it must be wired
back to the appropriate terminal on the
boiler PC Board.
Water Fill Valve — Maintains proper
water pressure in the central heating
circuit.
Back Flow Preventer — Use a back
flow preventer in the filling circuit to
the appliance as required by local code.
Dirt Trap — Protects the boiler from
debris in the plumbing system.
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents