ANNUALLY
Vent System
Inspect for blockages or damage.
Inspect vent screen or room air filter (if using) for debris and blockages.
Clean if needed.
Fan and Motors
Clean dust and dirt from fan and motor (motors are permanently lubricated
and do not require lubrication).
Controller
Clean by using a soft, damp cloth. Do not use solvents.
Pressure
Confirm the pressure is within the proper range (between 17-26 PSI). If the
pressure is lower than the specified range, add water until in the proper range.
Pressure Relief
Operate the pressure relief valve manually once a year. In doing so, it will be
Valve
necessary to take precautions with regard to the discharge of potentially
scalding hot water under pressure. Ensure discharge has a safe place to flow.
Contact with your body or other property may cause damage or harm.
discharged from the pressure relief valve could cause severe burns
instantly or death from scalds.
Heating System
Clean annually. Be sure to close the shut off valves under the boiler. After
Filter
cleaning and installing the filter, purge the air.
DHW Filter
If the flow volume of DHW is getting less, clean the filter at the DHW inlet. Be
sure to close the shut off valves on the DHW pipes under the boiler.
Expansion Tank
Perform annual checks as recommended by the manufacturer to ensure proper
operation.
Condensation
Check if the trap contains sediment. To remove sediment, unplug the bottom of
Trap
the condensate trap. Remove the sediment, and then return the plug. Do not
use a wrench to tighten the condensate drain as this could cause the
connection to break.
Condensation
Confirm the condensation drain line is not blocked or clocked.
Drain
Ensure the condensation drain pump (if utilized) is working correctly.
Flushing DHW
Flushing for DHW (plate heat exchanger). When LC code appears, the boiler
Heat Exchanger
detects lime scale accumulation. Once the flushing done, the LC code will
disappear automatically. If the boiler is installed in hard water area, Rinnai
recommends periodically flushing.
Draining Water
When the system will be shutdown for a long period of time (seasonal
shutdown), close the shutoff valves below the boiler and drain the boiler to
protect it from potential freeze damage.