Checking And Updating Iec 60870-5-103 Points; Reengineering In The Hmi Event Filtering Tool; Reengineering In Graphical Display Editor - ABB Relion Series Engineering Manual

Grid automation
Hide thumbs Also See for Relion Series:
Table of Contents

Advertisement

1MRS757810 C
8.5.4.3
8.5.5
8.5.6
REC615 and RER615
Engineering Manual
1.
Check the point list and verify that all the point types correspond to the old
configuration and Modbus master.
0X – Readable coils
1X – Discrete inputs
3X – Input registers
4X - Readable holding registers
Fault record data
If some points have different attributes, adjust them in the Communication
Management tool.
2.
Adjust possible missing points or changed point addresses in Modbus master
configuration.

Checking and updating IEC 60870-5-103 points

If IEC 60870-5-103 is used, the migrated IEC 60870-5-103 point list should for most
part correspond to the configuration made in the old IED.
1.
Check the point list and verify that all the point types correspond to the old
configuration and IEC 60870-5-103 master.
Indications
Measurands
2.
If some points have different attributes, adjust them in the Communication
Management tool.
3.
Change the possible changed point addresses to match the master address by
using a user-defined address instead of the default address.
4.
Adjust possible missing points points in IEC 60870-5-103 master configuration.

Reengineering in the HMI event filtering tool

If HMI event filtering is used, the migrated event filter should for most part
correspond to the configuration made in the old IED.
1.
Check the HMI event filter tree view and verify that the event filter corresponds
to the old configuration.
2.
Add or remove the possible missing events in the migrated configuration by
selecting or clearing the check box in the HMI event filtering tool.

Reengineering in Graphical Display Editor

Check and modify the single-line diagram in Graphical Display Editor for the
desired appearance and needed functionalities for the HMI.
Write the migrated configuration into the IED.
Section 8
Configuration migration
137

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615Relion rec615

Table of Contents