Section 5
Protection and control engineering
5.6
5.6.1
5.6.2
86
IED Compare
IED Compare is used to compare the IED configuration of two same type of IEDs. It
generates a text report which lists the differences in the IED configuration. IED
Compare provides an option to compare an IED configuration stored in PCM600, IED
or .pcmi file. IED Compare can compare certain types of IED configurations and
parameters.
•
Application configuration
•
Display configuration
•
GOOSE receive configuration
•
Parameters
Application comparison also compares the system function blocks.
Display comparison compares two display pages with a delta of two
pixels.
Detailed instructions are shown in PCM600 documentation.
Starting IED Compare
•
Start IED Compare in the context menu in plant structure.
1.
In the PCM600 plant structure, right-click Substation, Voltage level, Bay
or IED.
2.
Select IED Compare.
•
Start IED Compare from the PCM600 main menu.
1.
Select Substation, Voltage level, Bay or IED in the PCM600 plant
structure.
2.
On the PCM600 menu bar, point to Tools and select IED Compare.
IED Compare tool interface
The comparison report shows differences in the configuration of two IEDs. Hardware,
application, display, GOOSE and parameter configuration differences are grouped
and listed under the corresponding headings.
1MRS757810 C
REC615 and RER615