Function Blocks - ABB Relion Series Engineering Manual

Grid automation
Hide thumbs Also See for Relion Series:
Table of Contents

Advertisement

Section 5
Protection and control engineering
5.1.1
66
Document the application configuration: such as, make printouts
Save application configurations as templates in an application library to
reuse them in other protection relays (Function blocks and related logic can
be fully or partially reused depending on the functionality available in the
other protection relay)
Validate the application configuration during the configuration process on
demand and while writing the application configuration to the protection
relay
For instructions on how to perform the different tasks in PCM600, see
PCM600 online help.

Function blocks

Function blocks are the main elements of an application configuration. They are
designed for a various number of functions and organized into groups according to
type. The different function block types are shown in the Object Types view.
Function block data can be modified with the Application Configuration tool.
User-defined names can be given for function blocks and signals.
Signals that have a user-defined name created with the
Application Configuration tool are only visible in the Parameter
Setting tool if the relay configuration is written to the protection
relay and read back to PCM600. Otherwise, the default signal
name is shown in the Parameter Setting tool.
If possible, set the user-defined name to a signal before
connecting the signal to other function blocks.
IEC 61850, ANSI or IEC 60617 symbol standard can be set.
IEC or ANSI naming style can be set.
Function blocks can be locked.
Visibility for execution order, cycle time and instance number can be set.
Signals can be managed.
Boolean inputs and outputs can be inverted.
1MRS757810 C
REC615 and RER615
Engineering Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615Relion rec615

Table of Contents