Validation

Validation checks the application configuration for errors based on the rules that
govern the creation of the application at three different times.
During the logic creation, while making a connection or placing a function block
On demand by starting the validation
When writing the application configuration to the protection relay

Validation when creating an application configuration

Validation is made when creating the application configuration.
A connection between two input or two output signals is not possible
A connection between two different data types is not possible: for example, from
a binary output to an analog input

Validation on demand

The validity of an application configuration can be checked by clicking Validate
Configuration in the toolbar. The Application Configuration tool checks the
application configuration for formal correctness. The found problems are divided into
warnings and errors.
Warnings, marked with a yellow warning icon
Example: a variable connected to an output signal that is not connected
Example: if an output from a higher execution order function is connected
to inputs of lower execution order function
Errors, marked with a red circle with a cross
Example: unconnected hardware output
Warnings do not prevent writing to the protection relay. However, errors must be
corrected before writing the application configuration to the protection relay. The
application configuration can be saved and the Application Configuration tool can be
closed with open errors, but the application configuration cannot be written to the
protection relay.