System modifications in operation
14.7 Editing CPU parameters
14.7.3

Step B: Stopping the standby CPU

Starting situation
The fault-tolerant system is operating in redundant mode.
Procedure
1. In SIMATIC Manager, select a CPU of the fault-tolerant system, then choose "PLC >
2. From the "Operating Mode" dialog box, select the standby CPU, then click "Stop".
Result
The standby CPU switches to STOP mode, the master CPU remains in RUN mode, the
fault-tolerant system works in single mode. One-sided I/O of the standby CPU is no longer
addressed.
14.7.4

Step C: Loading new hardware configuration in the standby CPU

Starting situation
The fault-tolerant system is operating in single mode.
Procedure
Load the compiled hardware configuration in the standby CPU that is in STOP mode.
NOTICE
The user program and connection configuration can not be downloaded in single mode.
Result
The modified CPU parameters in the new hardware configuration of the standby CPU do not
yet have an effect on ongoing operation.
236
Operating Mode" from the menu.
System Manual, 09/2007, A5E00267695-03