S7-400H in PROFIBUS DP mode
7.1 CPU 41x–H as PROFIBUS DP master
Evaluation in the user program
The table below shows you how to evaluate RUN-STOP changes of the DP slave on the DP
master. See previous table.
On the DP master
Example of diagnostic addresses:
Master diagnostic address = 1023
Slave diagnostic address on master system = 1022
The CPU calls OB 82 with at least the following information:
OB82_MDL_ADDR: = 1022
OB82_EV_CLASS: = B#16#39
As event entering state
OB82_MDL_DEFECT: = module fault
The CPU diagnostic buffer also contains this information
Your user program should also be set up to read the diagnostic
data of the DP slave using SFC 13 "DPNRM_DG".
Use SFB 54 in the DPV1 environment. This outputs the full interrupt
information.
72
On the DP slave (CPU 41x)
Example of diagnostic addresses:
Slave diagnostic address = 422
Master diagnostic address = irrelevant
CPU: RUN → STOP
CPU generates a DP slave diagnostic frame.
System Manual, 09/2007, A5E00267695-03