Failure and replacement of components during operation
13.2 Failure and replacement of components during operation
13.2.5

Failure and replacement of a synchronization module or fiber-optic cable

In this section, you will see three different error scenarios:
● Failure of a synchronization module or fiber-optic cable
● Successive failure of the two synchronization modules or fiber-optic cables
● Simultaneous failure of the two synchronization modules or fiber-optic cables
The CPU displays by means of LEDs and by means of the diagnosis whether the lower or
upper redundant link has failed. After the defective parts (fiber-optic cable or synchronization
module) have been replaced, LEDs IFM1F and IFM2F go out.
Starting situation
Failure
Failure of a fiber-optic cable or synchronization
module:
The S7-400H is in redundant mode and a fiber-optic
cable or a synchronization module fails.
Procedure
Follow the steps below to replace a synchronization module or fiber-optic cable:
Step
1
2
3
4
5
6
7
192
What needs to be done?
First, check the fiber-optic cable.
Start the standby CPU (for example,
STOP-RUN or Start using the PG).
Remove the faulty synchronization
module from the standby CPU.
Insert the new synchronization module
in the standby CPU.
Plug in the fiber-optic cable connections
of the synchronization modules.
Start the standby CPU (for example,
STOP-RUN or Start using the PG).
If the standby CPU changed to STOP
in step 6:
Remove the synchronization module
from the master CPU.
How does the system react?
Master CPU reports the event in the diagnostic
buffer and with OB 72.
Master CPU remains in RUN mode; standby
CPU changes to STOP
The diagnostic LED on the synchronization
module is lit
How does the system react?
The following reactions are possible:
1. CPU changes to RUN mode.
2. CPU changes to STOP mode. In this case
continue at step 3.
The diagnostic LED on the synchronization
module goes off
Both CPUs report the event in the diagnostic
buffer
The following reactions are possible:
1. CPU changes to RUN mode.
2. CPU changes to STOP mode. In this case
continue at step 7.
Master CPU processes insert/remove-module
interrupt OB 83 and redundancy error OB 72
(entering state).
System Manual, 09/2007, A5E00267695-03