Parameters
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
Activates the set-up selection via a digital input.
input
[1]
Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2]
Logic
Activates the set-up selection via the fieldbus/
AND
serial communication port, and via 1 of the
digital inputs.
[3]
Logic OR
Activates the set-up selection via the fieldbus/
*
serial communication port, or via 1 of the
digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
fieldbus.
[0]
Digital
Activates preset reference selection via a digital
input
input.
[1]
Bus
Activates preset reference selection via the
serial communication port or fieldbus option.
[2]
Logic AND Activates preset reference selection via the
fieldbus/serial communication port, and via 1 of
the digital inputs.
[3]
Logic OR
Activates the preset reference selection via the
*
fieldbus/serial communication port, or via 1 of
the digital inputs.
8-90 Bus Jog 1 Speed
Range:
Function:
100 RPM
[ 0 - par. 4-13
Enter the jog speed. Activate this
*
RPM]
fixed jog speed via the serial port
or fieldbus option.
8-91 Bus Jog 2 Speed
Range:
Function:
200 RPM
[ 0 - par. 4-13
Enter the jog speed. Activate this
*
RPM]
fixed jog speed via the serial port
or fieldbus option.
10-00 CAN Protocol
Option:
Function:
NOTICE
The options depend on installed option.
[0] CANopen
[1] DeviceNet View the active CAN protocol.
MG92G102
Programming Guide
10-01 Baud Rate Select
Select the fieldbus transmission speed. The selection must
correspond to the transmission speed of the master and the
other fieldbus nodes.
Option:
[16]
[17]
[18]
[19]
[20]
[21]
[22]
10-02 MAC ID
Range:
Size related
10-05 Readout Transmit Error Counter
Range:
0
[0 - 255 ] View the number of CAN control transmission
*
10-06 Readout Receive Error Counter
Range:
0
[0 - 255 ] View the number of CAN control receipt errors
*
10-33 Store Always
Option: Function:
[0]
Off Deactivates non-volatile storage of data.
*
[1]
On
10-50 Process Data Config. Write
Only elements [2] and [3] of this array can be selected ([0] and
[1] are fixed).
Option:
[0]
*
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
Danfoss A/S © 06/2015 All rights reserved.
10 Kbps
20 Kbps
50 Kbps
100 Kbps
125 Kbps
250 Kbps
500 Kbps
Function:
[ 0 - 127] Selection of station address. Every
*
station connected to the same network
must have an unambiguous address.
Function:
errors since the last power-up.
Function:
since the last power-up.
Stores parameter data received via VLT
MCA 104 in EEPROM non-volatile memory as default.
None
16-80 Fieldbus CTW 1
16-82 Fieldbus REF 1
3-02 Minimum Reference
3-03 Maximum Reference
3-12 Catch Up/Slow Down Value
3-41 Ramp 1 Ramp Up Time
3-42 Ramp 1 Ramp Down Time
3-51 Ramp 2 Ramp Up Time
3-52 Ramp 2 Ramp Down Time
3-80 Jog Ramp Time
3-81 Quick Stop RampTime
4-11 Motor Speed Low Limit (RPM)
4-13 Motor Speed High Limit (RPM)
Function:
6
®
DeviceNet
Function:
33
6