Configuration
Object
NMT
3
3
SYNC
Time stamp
EMERGENCY
PDO1 (tx)
PDO1 (rx)
PDO2 (tx)
PDO2 (rx)
PDO3 (tx)
PDO3 (rx)
PDO4 (tx)
PDO4 (rx)
SDO (tx)
SDO (rx)
NMT error control
(Nodeguarding)
Table 3.2 Communication Object
Transmit and receive is always seen from the node's point
of view:
RX = Nodes receiving data (Controller -> node)
TX = Nodes transmitting data (node -> controller)
Example:
COB-ID 383 = PDO3 transmit, from node address
3.
COB-ID 185 = PDO1 transmit, from node address
5.
COB-ID 604 = SDO receive, to node address 4.
3.1.3 Controlling the Network
In each CANopen node, a state machine controls the
different states of the node.
After power-up, the node transmits a boot-up message
with the COB-ID: 700h + Node ID, and goes from initiali-
sation to pre-operational state.
In this state, SDO communication is possible, but not PDO
communication.
8
VLT
Function
Resulting COB-ID Communi-
code
cation
(binary)
parameter in
OD
0000
0
0001
125
(1005h)
0010
256
0001
129 (81h)–255
1014h
(FFh)
0011
385 (181h)–511
1800h
(1FFh)
0100
513 (201h)–
1400h
639(27Fh)
0101
641 (281h)–
1801h
767(2FFh)
0110
769 (301h)–895
1401h
(37Fh)
0111
897 (381h)–1023
1802h
(3FFh)
1000
1025 (401h)–1151
1402h
(47Fh)
1001
1153 (481h)–1279
1803h
(4FFh)
1010
1281 (501h)–1407
1403h
(57Fh)
1011
1409 (581h)–1535
1200h – ...
(5FFh)
1100
1537 (601h)–1663
1200h – ...
(67Fh)
1110
1793 (701h)–1919
1016h, 1017h
(77Fh)
(100Eh)
Danfoss A/S © 06/2015 All rights reserved.
®
CANopen MCA 105
The node must have a start network-command from an
NMT-master to enter the operational state.
In operational state, both SDO and PDO communication
are possible.
The NMT-state of the node is displayed with the green NS
LED:
Flashing = Pre-operational.
Solid on = Operational.
Single flash = Stopped.
A reset node or reset communication-command from the
NMT-master makes the node jump to initialisation state
and directly on to pre-operational state.
Illustration 3.3 Controlling the Network
3.1.4 Error Control
CANopen offers 2 ways of error-control: Node guarding
and Heartbeat.
In node guarding, the NMT-master sends a remote-frame
(RTR) cyclically: 700 + node ID.
The node replies with its actual status.
The node (frequency converter) monitors the reception of
the RTR-frames, and thereby monitors the presence of the
NMT-master.
Configure the monitoring of the NMT-master via:
OD: 100C Guard time in [ms].
OD: 100D Life time factor.
If Guard Time x Life Time Factor has expired, the action
programmed in the parameter 8-04 Control Word Timeout
Function is executed.
MG92G102