Automationdirect.com Productivity 2000 P2-16AD-1 Manual

Automationdirect.com Productivity 2000 P2-16AD-1 Manual

Analog input

Advertisement

Quick Links

WARNING:

To minimize the risk of potential safety problems, you
should follow all applicable local and national codes that regulate the
installation and operation of your equipment. These codes vary from
area to area and it is your responsibility to determine which codes
should be followed, and to verify that the equipment, installation, and
operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from
the failure to follow all applicable codes and standards. We do not
guarantee the products described in this publication are suitable for
your particular application, nor do we assume any responsibility for
your product design, installation, or operation.
If you have any questions concerning the installation or operation
of this equipment, or if you need additional information, please call
Technical Support at 770-844-4200.
This publication is based on information that was available at the
time it was printed. At AutomationDirect.com
improve our products and services, so we reserve the right to make
changes to the products and/or publications at any time without
notice and without any obligation. This publication may also discuss
features that may not be available in certain revisions of the product.

Connector Specifications

Connector Type
24-Pin Molex Style 43025-2400
Number of Pins
24
Pin Spacing
3x3 mm (0.118 x 0.118 in)
Sales 800-633-0405
we constantly strive to
®
2000
P2-16AD-1 Analog Input
The P2-16AD-1 Current Analog Input
1
1 4 . 5 4
M
A
Module provides sixteen channels for
2
0 3 . 2 3
M
A
3
7 . 2 3
M
A
4
U N D E R
receiving 0-20 mA signals for use with
5
3 . 2 3
M
A
6
O V E R
the Productivity2000
7
2 . 3 2
M
A
8
S P A R E
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Connector Specifications . . . . . . . . . . . . . . . . . . . . . 1
General Specifications . . . . . . . . . . . . . . . . . . . . . . 2
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hot Swap Information . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . 6
OLED Panel Display Menus . . . . . . . . . . . . . . . . . . 7
Warranty: Thirty-day money-back guarantee. Two-year limited replacement.
(See www.productivity2000.com for details).
www.productivity2000.com
System.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Productivity 2000 P2-16AD-1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Automationdirect.com Productivity 2000 P2-16AD-1

  • Page 1: Table Of Contents

    This publication is based on information that was available at the General Specifications ..... . 2 time it was printed. At AutomationDirect.com we constantly strive to ®...
  • Page 2: General Specifications

    General Specifications Input Specifications Operating Temperature 0º to 60ºC (32º to 140ºF) Input Channels 16 sinking Storage Temperature -20º to 70ºC (-4º to 158ºF) Module Signal Input Range 0–20 mA Humidity 5 to 95% (non-condensing) Signal Resolution 16-bit Resolution Value of LSB 0–20 mA = 0.305μA per count Environmental Air No corrosive gases permitted...
  • Page 3: Wiring Diagram And Schematic

    Wiring Diagram Schematic Current Input Circuits INTERNAL An Edison S500-32-R 0.032A fast-acting MODULE fuse is recommended for current loops. CIRCUITRY – fuse .032A 2-Wire 4-20 mA – Transmitter +24VDC User CH1 ADC Supplied Power CH5 ADC CH2 ADC 2-Wire Transmitter CH6 ADC CH3 ADC CH7 ADC...
  • Page 4: Module Installation Procedure

    Before attempting to use the hot- swap feature, be sure to read the hot-swap topic in the programming software’s help file or our online documen- tation at AutomationDirect.com for details on how to plan your installation for use of this powerful feature. www.productivity2000.com...
  • Page 5: Wiring Options

    Module Configuration Wiring Options ZIPLink Connection System Cable + ZIPLink Module = Complete System Using the Hardware Configuration tool in the ZIPLink pre-wired Productivity Suite programming software, drag terminal block cables and drop the P2-16AD-1 module into the base configuration. Select Automatic Module Verification or No 0.5m (1.6 ft) cable ZL-P2-CBL24...
  • Page 6: Linear Scaling

    Linear Scaling Non-Linear Scaling The Scale (Linear) function can be used to: The Scale (Non-Linear) function can be used for Non-Linear applications. • Convert analog field input signals from the range which is native to the analog input module to an application specific range. •...
  • Page 7: Oled Panel Display Menus

    OLED Panel Display Power On Hold SEL button down to cycle through primary screens. Release button to select screen. Appears DISPLAY DISPLAY DISPLAY PASSED DISPLAY DISPLAY initially UNITS UNITS UNITS SELF SETUP STATUS DECIMAL MILLIAMP TEST INFO INFO COUNTS COUNTS 0-20mA These screens will then auto cycle...
  • Page 8 Document Name Edition/Revision Date P2-16AD-1-DS 1st Ed., Rev. A 4/26/2018 Copyright 2018, AutomationDirect.com Incorporated/All Rights Reserved Worldwide www.productivity2000.com Tech Support 770-844-4200...