The immunity requirements should follow product standard IEC 61800-3. See Table 2.12 for details.
Voltage range: 380–480 V
Product standard
Test
Acceptance criterion
Mains cable
Motor cable
Brake cable
Load sharing cable
Relay cable
Control cable
Standard/fieldbus cable
LCP cable
Enclosure
Table 2.12 EMC Immunity Requirements
Definition:
CD: Contact discharge
AD: Air discharge
DM: Differential mode
CM: Common mode
CN: Direct injection through coupling network
CCC: Injection through capacitive coupling clamp
MG06B402
Design Guide
ESD
Radiated immunity
B
B
4 kV CD
10 V/m
8 kV AD
Danfoss A/S © 09/2014 All rights reserved.
61800-3
Burst
Surge
B
A
2 kV/2 Ω DM
2 kV CN
2kV/12 Ω CM
4 kV CCC
4 kV CCC
4 kV CCC
4 kV CCC
length>2m
Unshielded:
1 kV/42 Ω CM
1 kV CCC
length>2m
Unshielded:
1 kV/42 Ω CM
1 kV CCC
length>2m
1 kV CCC
2
2
Conducted
immunity
A
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS