Testing RIM functionality

Once the programming of the Wireless RIMs is complete, it is recommended that their
functionality is fully tested to ensure correct operation.
Below are some testing recommendations to ensure correct functionality.
Cause & e ect programmed for linking a zone of devices to a RIM.
Activate a device into a re alarm condition, in a zone which also has a RIM allocated to that
zone.
Ensure that the device operated into an alarm condition's LED illuminates, together with
the LED of the RIM associated with the zone.
Silence the control panel. The LEDs will still be illuminated.
Reset the re alarm condition on the control panel. The activated device and the associated
RIM's LEDs will extinguish.
Repeat the above test for each device in the zone. On each occasion the RIM's LED will
operate and follow the operation as described above.
Note: The RIM LED will only illuminate for re alarm activations in the associated Zone. The LED
should not illuminate for any other activations.
Cause & e ect programmed for linking an INDIVIDUAL DEVICE to a Remote Indicator
Module.
Activate a device into a re alarm condition which also has an associated Wireless RIM .
Ensure that the device operated into an alarm condition's LED illuminates, together with
the LED of the device's associated RIM.
Silence the Control panel. The LED's will still be illuminated.
Reset the re alarm condition on the control panel. The activated device and the associated
RIM's LEDs will extinguish.
Note: The RIM LED will only illuminate for Fire Alarm activations from the allocated device. The
LED should not illuminate for any other activations.