1 Pre installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if
mounting the device on to a metal surface.
DO NOT press the log on button on a pre-programmed
device. This will cause communication with the control panel
to be lost. Should this happen, delete the device from the
system and add it back on.
This device contains electronics that may be susceptible to
damage from Electrostatic Discharge (ESD). Take appropriate
precautions when handling electronic boards.
3 Disassemble device
First disengage the remote indicator from the wireless module
by turning it anticlockwise. This exposes the wireless module's
locking pin as shown.
Disengage
the
mounting
plate by turning the wireless
module anticlockwise, whilst
pressing down the locking
pin.
5 Power device
When fitting / replacing batteries; observe correct polarity,
using only specified batteries.
Connect the power jumper across the PIN header.
device
unpowered
(pins unlinked)
device
powered
(both pins linked)
Once powered, reassemble the device.
©2021 EMS Ltd. All rights reserved
Example shown:
Model FCX-178-001
Locking pin
www.emsgroup.co.uk
Wireless Detector Base
Part No: FCZ-170-111
PRESS HERE TO
LOG ON
www.emsgroup.co.uk
Wireless Detector Base
Part No: FCZ-170-111
PRESS HERE TO
LOG ON
Page 1 of 2
Part no
Product description
FCX-178-001
Wireless Remote Indicator Module
FCZ-170-111
Remote Indicator Wireless Module Only
117261
Remote Indicator Only
2 Components
1
1
Remote indicator
2
4 Fix mounting plate
When wall mounting, ensure the mounting plate is fitted in the
orientation shown.
Use all four mounting holes to ensure a firm fixing.
Use suitable fasteners and fixings.
6 Optional locking
To lock the remote indicator
into the wireless module,
remove the cut out section
as shown.
2
3
Wireless module
Mounting plate
3
THIS WAY UP
WHEN WALL
MOUNTING
TSD116-99 Iss 5 24/11/2021
AJM

Advertisement

loading

Summary of Contents for EMS fireCell FCX-178-001

  • Page 1 (pins unlinked) www.emsgroup.co.uk Wireless Detector Base Part No: FCZ-170-111 device powered PRESS HERE TO (both pins linked) LOG ON Once powered, reassemble the device. ©2021 EMS Ltd. All rights reserved Page 1 of 2 TSD116-99 Iss 5 24/11/2021...
  • Page 2 Part 25: Components using radio links IP rating IP23 European Union EMS declares that this device is in compliance with directives Directive 2014/53/EU. The full text of the EU Operating declaration of conformity is available at the...

This manual is also suitable for:

Firecell fcz-170-111Firecell 117261