The Liebert Global Products MIB is available at
download/monitoring/management-information-bases-mibs-for-liebert-products/. It supports both
®
Windows
(192436P1) and Unix (192435P1) file formats.
Configure SNMP Settings
SNMPv3 Users or SNMPv1/v2c Trap and Access settings must be made before SNMP access or
notifications can occur. The Unity card permits up to 20 SNMPv3 Users, up to 20 SNMPv1 Trap targets,
and up to 20 SNMPv1/v2c Access addresses.
The required changes vary according to the type of SNMP protocol used:
•
SNMPv1 must have trap settings.
•
SNMPv2c must have Access settings.
•
SMPv3 users must have settings configured and the method for generating the Engine ID may
be selected.
•
the access settings for SNMPv1/v2c are separate from SNMPv1 trap settings.
Select SNMPv3 Engine ID Format
By default, the Engine ID is automatically generated using the MAC address. Optionally, you can select a
text-based ID instead.
1.
On the Communications tab, select Protocols > SNMP.
2. Click Edit, and enter a user name and password if necessary.
3. Edit the settings:
Refer to
•
In SNMPv3 Engine ID Format Type, select MAC Address or Text.
•
If you selected Text, type the text on which the generated engine ID will be based.
•
Click Save to confirm the changes or Cancel to discard them.
The new engine ID is not displayed until after rebooting the card in Step 4.
The text-generated engine ID is a hexadecimal representation of ASCII characters similar
to that shown in Figure 3.1 on the next page.