2.2 Change User Names and Passwords Immediately
NOTE: We recommend changing the user names and passwords of the factory-default Local Users
with administrator and general access immediately to safeguard protected configuration and control
areas of the Unity card.
The factory-default administrator user is "Local Users [1]" with the user name Liebert and default
password Liebert (both case-sensitive).
The factory-default general user is "Local Users [2]" with the default password Liebert (case-sensitive).
To change the user names and passwords, see the steps in
2.3 Configure the Card
The Unity card requires minor configuration, to enable basic network connectivity. The default for IP/Web
communication is IPv4, but this can be changed to IPv6 for greater security. Contact your network
administrator to determine if it is compatible with your network.
1.
On the Communications tab menu, select Configuration > Network.
2. Enable the protocol, IPv4 or IPv6, that will be used to communicate with the Unity card and
with the Liebert equipment:
a. Click IPv4 or IPv6.
b. Click Edit.
c. When prompted, enter the Administrative user name and password.
The default name and password are both "Liebert" (case-sensitive).
d. Click to check enabled.
e. Enter the assigned IP address along with the rest of the required networking information.
Contact your system administrator if necessary.
3. Click Save to confirm the changes or Cancel to discard them.
The changes take effect after the card is restarted.
2.4 Installing Multiple Cards in a System
More than one Liebert IntelliSlot card may be installed in a system, but circular routes and duplicate node
IDs must be avoided during installation. The following instructions apply when the second card to be
installed is an IntelliSlot Unity card. If the second card is not a Liebert IntelliSlot Unity card, follow
instructions in the user manual for that card.
Before beginning installation of a second Unity card, verify that the first card functions properly.
If the first card is an IntelliSlot card, but not a Unity card, and if both cards connect to the same Ethernet
network, then you should disable the router function on the first card. This will avoid circular routes. Follow
instructions in the user manual for the first card.
If the first and second cards are both IntelliSlot Unity cards, steps must be taken to avoid duplicate
Velocity Protocol MSTP node IDs. By default, the two cards would use the same node ID, and one or both
cards would report a duplicate node error and fail to communicate with the system.
2 Installation
Local Users Folder
on page 31.