Section 7
Troubleshooting
7.2.2
7.2.3
86
Table 15:
Internal fault indications
Fault indication
Internal Fault
Real Time Clock Error
Internal Fault
Runtime Exec. Error
Internal Fault
SW Watchdog Error
Internal Fault
Runtime App Error
Internal Fault
File System Error
Internal Fault
TRM-Error
Internal Fault
COM-Error
Internal Fault
PSM-Error
Internal Fault
RTD Error
Warnings
The warning message associated with the fault is found in the internal event list in the
LHMI menu Main menu/Monitoring/Internal events. The message includes the
date, time, description and signal state for the fault. The current status of the internal
fault signals can also be checked via the LHMI in Main menu/Monitoring/IED
status.
When a fault appears, record the fault indication message and state it when ordering
service.
Table 16:
Warning indications
Warning indication
Warning
IEC 61850 Error
Warning
DNP3 Error
Additional indications
The additional indication messages do not activate internal fault or warning.
Additional information
Hardware error with the real time clock.
One or more of the application threads
are not working properly.
This signal will be activated when the
terminal has been under too heavy load
for at least 5 minutes.
One or more of the application threads
are not in an expected state.
A file system error has occurred.
A TRM card error has occurred. The
instance number is displayed at the end
of the fault indication.
A COM card error has occurred. The
instance number is displayed at the end
of the fault indication.
A PSM card error has occurred. The
instance number is displayed at the end
of the fault indication.
An RTD card error has occurred. The
instance number is displayed at the end
of the fault indication.
Description
IEC 61850 has not succeeded in some actions
such as reading the configuration file or startup.
Error in DNP3 communication
1MRS756509 E
630 series