Controlling; Controlling Circuit Breakers And Disconnectors - ABB Relion 630 Series Operation Manual

Protection and control
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 6
Operating procedures
6.2
6.2.1
74
For more information, see the PCM600 documentation.

Controlling

Controlling circuit breakers and disconnectors

Before the control via LHMI is possible, the R/L button has to be in local position.
The primary equipment can be controlled via the LHMI with the Open and Close
buttons when the IED is set to local control mode and the user is authorized to access
control operations.
1.
Select Main menu/Control.
The SLD displays all controllable objects.
2.
Select an object with
Selection of object is indicated with a square border that moves when
are used.
Switch objects can have additional icons that present the switch object states.
Switch object is in substituted state.
Switch object is interlocked.
3.
Press
to open or
GUID-B91C8F52-F264-40F3-A869-614A686A19A4 V1 EN
Figure 55:
Selecting an object
4.
Press
to confirm the operation.
or
.
to close the object.
1MRS756509 E
and
630 series
Operation Manual