7 Troubleshooting

Problems with the option interface may trigger an operator error.
Refer to the J1000 Technical Manual for all other errors.
Fault
LED Operator
Display
Cause
Data not received
within the CE
detection time
limit set in
parameter H5-09.
This is possibly
due to noise or a
improperly
connected
communication
cable.
YASKAWA ELECTRIC TOBPC73060033A RS-485 Interface Technical Manual
MEMOBUS/Modbus Communication
CE
Error
Possible solutions
• Check for improper wiring or loose cables.
• Make sure the unit is properly grounded.
• Reconnect leads running to the main
circuit in the drive. Make sure the DIP
switch for terminal resistance is set
appropriately.
• Make sure the DIP switch for terminal
resistance is set appropriately.
7 Troubleshooting
Minor Fault Name
23