5.4.3.3

Meaning of the LEDs on the control supply module

Table 5-8
Control Supply Module - Description of the LEDs
LED
Color
READY
-
Green
DC LINK
-
Yellow
Red
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
State
Description
OFF
Electronics power supply outside permissible tolerance range
Continuous
Ready for operation. Output voltage within tolerance range
OFF
DC input voltage < 290 V
Continuous
DC input voltage in the range 370 < Ue < 820 V
Floating operation possible
Continuous
DC input voltage outside the tolerance range.
DC input voltage 290 V< Ue < 370 V or Ue > 820 V
DC link components Booksize
5.4 Control Supply Module (CSM)
, floating operation not possible
DC
DC
DC
5-21