Line Connection Booksize
2.4 Wideband Line Filter for Active Line Modules
2.4.3.1

Line/load connection

A Wideband Line Filter for Active Line Modules is rated for a voltage range of 380 V
3AC -10% to 480 V 3AC +10% (-15% <1 min) at 47 Hz to 63 Hz.
Table 2-5
Type of connection
Terminals
Line connection (line)
Load connection (load)
Wideband Line Filter for Active Line Modules
16 kW
36 and 55 kW
80 kW
120 kW
1) for ring cable lugs to DIN 46234
2-12
Designations
L1, L2, L3, PE
U, V, W
Screw terminal: 10 mm
3-pin/1.5 Nm (see Screw Terminals)
2
Ground stud: M5/3 Nm
1)
Screw terminal: 50 mm
3-pin/6 Nm (see Screw Terminals)
2
Ground stud: M8/13 Nm
1)
Screw terminal: 95 mm
3-pin/15 Nm (see Screw Terminals)
2
Ground stud: M8/13 Nm
1)
Connection strap: d = 11 mm (M10/25 Nm)
Ground stud: M8/13 Nm
1)
Note: No shock-hazard protection (IP00)